Product overview

YBFC is a YORK hydronic fan coil family with concealed ceiling and concealed vertical arrangements. Coil rows, water circuit, motor and external static pressure are selection variables. The table below covers only the 2-pipe, 3-row AC-motor configuration at high speed; it is not a universal rating for all YBFC units.

BUYING FROM EXISTING INVENTORY

Wholesale Purchasing Information

New, unused YORK equipment, originally supplied in factory packaging. Based on our current inventory records, most YORK main units are from 2022 or later production batches. The manufacturing date and condition of each offered unit will be verified before order acceptance.

  1. Identify the equipmentSend the full model, quantity, destination, power supply and required configuration.
  2. Review a batch-specific offerReview equipment condition, available quantity, agreed pre-shipment checks and model-specific electrical/configuration suitability.
  3. Agree the order termsThe formal quotation records the equipment, pricing, shipment scope, delivery arrangements and applicable warranty/claims terms.

Configuration and support before ordering

Certain main units may be opened for regional configuration by Delta M&E personnel and repacked before shipment. Feasibility is checked by exact model; this is not a claim of manufacturer authorization. Factory-sealed condition and manufacturer warranty must not be assumed after adjustment.

Smart Panel functionality is not supported on affected units after regional configuration. Future availability or restoration is not guaranteed and must not be relied upon as a purchasing assumption. This concerns IWE Smart Panel, not every thermostat, controller or app.

Operating functions, controller compatibility and connectivity must be verified for the exact model and system configuration. Only functions expressly confirmed in the relevant quotation or technical records should be relied upon.

Overseas installation, on-site commissioning and routine local after-sales service are not included by default. Verified seller-responsible defects remain eligible for appropriate remedies. Relevant limitations and buyer acknowledgments are recorded in the actual quotation or sales agreement before order acceptance.

Inventory model references

Technical Documents

  • YORK YBFC Fan Coil Units — English Catalog

    English · Product catalog · PUBL-6658 (0121) · APAC brochure

    Applicable to the documented YBFC02/03/04/05/06/07/08/10/12/14 size references with 2-pipe, 3-row, S/H (12/30 Pa) configurations shown on this page. Other coil, motor, installation and static-pressure configurations require their own selection data. Specifications may vary by model revision and market. Confirm the exact model before ordering.

Key technical specifications

Manufacturer catalog: YORK YBFC / YKFC / YJFC · Edition: PUBL-1788ZH (0224) · Reference PDF pages: 2, 4.

YBFC: 2-pipe, 3-row, AC motor — S / H configurations

CC / CB / CD arrangements from the 2-pipe, 3-row table. S = 12 Pa; H = 30 Pa. Size references below are not complete order codes. Values must not be transferred to 2-row, 4-pipe, U (50 Pa) or YBFC-K EC-motor configurations.

YBFC: 2-pipe, 3-row, AC motor — S / H configurations. CC / CB / CD arrangements from the 2-pipe, 3-row table. S = 12 Pa; H = 30 Pa. Size references below are not complete order codes. Values must not be transferred to 2-row, 4-pipe, U (50 Pa) or YBFC-K EC-motor configurations.
Model referenceExternal static pressure(Pa)Airflow (high speed)(m³/h)Total cooling capacity(kW)Heating capacity(kW)Voltage(V)Frequency(Hz)
YBFC02 / S123402.433.7722050
YBFC02 / H303402.453.822050
YBFC03 / S125203.45.3822050
YBFC03 / H305203.455.4622050
YBFC04 / S126804.226.9822050
YBFC04 / H306804.226.9822050
YBFC05 / S128505.28.1722050
YBFC05 / H308505.168.122050
YBFC06 / S1210206.410.1322050
YBFC06 / H3010206.410.1322050
YBFC07 / S1211906.6810.8322050
YBFC07 / H3011906.6810.8322050
YBFC08 / S1213608.613.3322050
YBFC08 / H3013608.513.1822050
YBFC10 / S1217109.116.1622050
YBFC10 / H3017109.115.9622050
YBFC12 / S12204011.4518.4122050
YBFC12 / H30204011.318.3822050
YBFC14 / S12238013.622.1622050
YBFC14 / H30238013.522.1622050
  • Cooling rating: return air 27 °C dry bulb / 19.5 °C wet bulb; entering water 7 °C; water temperature rise 5 °C; high fan speed.
  • Heating rating: return air 21 °C dry bulb; entering water 60 °C; high fan speed.
  • The model nomenclature specifies a single-phase AC motor at 220 V / 50 Hz for the standard motor option. Return-box selection and complete model suffixes must be confirmed separately.
  • Brochure ratings apply only to the listed model references and configuration. Confirm the complete model code, nameplate and current technical selection before procurement. They do not establish stock, export suitability or lead time.

Key configuration options

  • CC: concealed ceiling; CD: concealed ceiling with bottom-return box; CB: concealed ceiling with rear-return box. A return box is a selected arrangement, not standard on every model.
  • S = 12 Pa; H = 30 Pa; U = 50 Pa. This table includes only S and H configurations.
  • The family also includes 2-row and 4-pipe (3+1 row) selections. Their ratings are separate.
  • YBFC-K EC-motor options, left/right connections, filters and drain-pan options require their own complete model selection.

Applications

  • Room cooling and heating connected to a chilled / hot-water system
  • Concealed ceiling installations; arrangement depends on the complete order code

Information for equipment selection

  • Complete model code and required configuration
  • Cooling / heating duty and design water / air conditions
  • Electrical supply, quantity and project location
  • Installation arrangement and availability requirements

Related series

REQUEST A QUOTE / TECHNICAL INFORMATION

Request a model-specific wholesale offer

Product reference: YORK YBFC Series

Send the full model, quantity and destination. We will review the offered unit, configuration and agreed delivery scope for your formal quotation.

Review Warranty & After-Sales Support and Returns & Claims before ordering.

Email your requirements to [email protected]. You can include your BOQ or equipment schedule. See what to include in your inquiry.