Hitachi Cooling & Heating / SERIES OVERVIEW

Hitachi G Series

Air-Cooled Scroll Chiller / Heat Pump

Brand
Hitachi Cooling & Heating
Series
G
Equipment category
Heat Pumps
Request Technical Information
Hitachi G air-cooled scroll chiller / heat pump series reference image

Product overview

G-Series modular air-cooled equipment uses R410A and hermetic scroll compressors. Standard A, all-year AN and low-temperature AL configurations have different operating envelopes. The tables show individual module ratings; combined plant duty requires a separate selection.

Key technical specifications

Manufacturer catalog: Hitachi G · Edition: Z0050024-260514 · Reference PDF pages: 4–5.

G: standard / all-year heat-pump modules

Standard A and all-year AN variants share the printed nominal ratings; their operating envelopes differ. These are single-module ratings, not capacities for a multi-module assembly.

G: standard / all-year heat-pump modules. Standard A and all-year AN variants share the printed nominal ratings; their operating envelopes differ. These are single-module ratings, not capacities for a multi-module assembly.
Model referenceCooling capacity(kW)Cooling input power(kW)Heating capacity(kW)Heating input power(kW)Main power supplyRefrigerantCompressor typeLength(mm)Width(mm)Height(mm)Net weight(kg)CSPF (brochure)(dimensionless)
RHUA021A-GRequest a QuoteDiscuss This Model (opens WhatsApp in a new tab)6521.16721.3380 V / 3 phase / 50 HzR410AHermetic scroll190097019605403.55
RHUA041A-GRequest a QuoteDiscuss This Model (opens WhatsApp in a new tab)1304113341.8380 V / 3 phase / 50 HzR410AHermetic scroll2220111021608003.6
RHUA021AN-GRequest a QuoteDiscuss This Model (opens WhatsApp in a new tab)6521.16721.3380 V / 3 phase / 50 HzR410AHermetic scroll190097019605403.55
RHUA041AN-GRequest a QuoteDiscuss This Model (opens WhatsApp in a new tab)1304113341.8380 V / 3 phase / 50 HzR410AHermetic scroll2220111021608003.6
  • Cooling: leaving water 7 °C, water flow 0.172 m³/(h·kW), outdoor dry bulb 35 °C. Heating: leaving water 45 °C, same flow coefficient, outdoor dry bulb / wet bulb 7/6 °C.
  • Standard A models (RHUA021A-G / RHUA041A-G): cooling ambient 15–45 °C; heating ambient −15–25 °C. All-year AN models (RHUA021AN-G / RHUA041AN-G): cooling and heating ambient −15–45 °C. Cooling/heating leaving-water ranges remain 5–15 / 35–50 °C. Source: G-series brochure Z0050024-260514, PDF page 4 (printed page 05), operating-condition table and diagram. These are operating envelopes, not the nominal heating test point; consult the variable-condition performance tables for duty at the selected conditions.
  • CSPF is the brochure seasonal index, not instantaneous COP or a guaranteed project energy-saving rate.
  • Brochure reference ratings are not a current stock or delivery guarantee. Confirm the complete configuration, nameplate, destination-market requirements and current selection before procurement.

G: low-temperature AL heat-pump modules

Separate AL configuration. Standard heating, nominal low-ambient heating and lower-temperature heating have distinct test conditions; do not compare them without those conditions.

G: low-temperature AL heat-pump modules. Separate AL configuration. Standard heating, nominal low-ambient heating and lower-temperature heating have distinct test conditions; do not compare them without those conditions.
Model referenceCooling capacity(kW)Cooling input power(kW)Standard heating (7 °C air)(kW)Standard heating input(kW)Heating (−12 °C air)(kW)Heating (−20 °C air)(kW)APF (brochure)(dimensionless)Main power supplyRefrigerantCompressor typeLength(mm)Width(mm)Height(mm)Net weight(kg)
RHUA026AL-GRequest a QuoteDiscuss This Model (opens WhatsApp in a new tab)7423.18223.752433.28380 V / 3 phase / 50 HzR410AHermetic scroll187010301960600
RHUA051AL-GRequest a QuoteDiscuss This Model (opens WhatsApp in a new tab)14547.515546.5102813.27380 V / 3 phase / 50 HzR410AHermetic scroll221011502250940
  • Cooling: leaving water 7 °C; outdoor dry bulb 35 °C; water flow 0.172 m³/(h·kW). Standard heating: leaving water 45 °C, outdoor dry bulb / wet bulb 7/6 °C, same flow coefficient.
  • Nominal heating: leaving water 41 °C, outdoor dry bulb −12 °C / wet bulb −13.5 °C. Low-temperature heating: leaving water 41 °C, outdoor dry bulb −20 °C. These values are not the standard 7 °C heating rating.
  • AL envelope: cooling ambient 10–48 °C and leaving water 5–20 °C; heating ambient −30–30 °C and leaving water 35–60 °C. Confirm duty at the actual design point.
  • APF is the brochure seasonal index, not interchangeable with the standard-model CSPF or a project energy-saving percentage.
  • Brochure reference ratings are not a current stock or delivery guarantee. Confirm the complete configuration, nameplate, destination-market requirements and current selection before procurement.

Key configuration options

  • Standard and AN all-year configurations share nominal ratings but have different cooling and heating ambient ranges.
  • Low-temperature AL models have their own capacity table, water-side heat exchanger and test conditions.
  • No screw, centrifugal or inverter-compressor configuration is inferred from the G-series name.

Applications

  • Modular hydronic cooling / heating
  • Project-specific outdoor chiller / heat-pump equipment selection

Information for equipment selection

  • Complete model / configuration and equipment schedule
  • Required duty and design water / ambient conditions
  • Power supply, installation space and project location
  • Destination-market requirements and current availability confirmation

Technical Documents

Request Technical Information

Related series

REQUEST A QUOTE / TECHNICAL INFORMATION

Discuss your project equipment

Product reference: Hitachi G Series

Send your BOQ or equipment schedule, cooling/heating capacity, application, project location, design requirements, power supply and expected procurement timeline. Installation, commissioning and after-sales arrangements can be included where expressly agreed for the project.