Hitachi Cooling & Heating / SERIES OVERVIEW

Hitachi AZ2 / AZP2 / AZX Air-Cooled Screw Chillers & Heat Pumps

Air-cooled screw chiller / heat pump

Brand
Hitachi Cooling & Heating
Series
AZ2 / AZP2 / AZX
Equipment category
Chillers

Product overview

AZ2, AZP2 and AZX are R134a air-cooled screw equipment selections, each with 12 listed sizes and separate RCUF and RHUF references. The subseries retain their own input power, COP, seasonal index, dimensions and weights. RHUF heating ratings are shown at their separate test point. These tables describe the conventional screw configurations in this brochure and are independent of the inverter-driven AVX series.

Key technical specifications

Match the complete model and configuration to your design duty. Compare ratings only at the stated water and ambient conditions; then send the model reference, quantity and project requirements for review.

Scroll each table horizontally to compare all columns. Model references remain visible as you scroll.

AZ2 / RCUF — cooling-only performance

Fixed-speed semi-hermetic twin-screw chillers. RCUF and RHUF are separate model selections.

AZ2 / RCUF — cooling-only performance. Fixed-speed semi-hermetic twin-screw chillers. RCUF and RHUF are separate model selections.
Model referenceCooling capacity(kW)Cooling input power(kW)Cooling COP(W/W)CSPF(dimensionless)Cooling rated current(A)Cooling maximum current(A)
RCUF150AZ2Request a Quote489153.83.183.8257385
RCUF180AZ2Request a Quote604191.73.153.8320480
RCUF200AZ2Request a Quote6522053.183.8342513
RCUF300AZ2Request a Quote978307.53.183.8514770
RCUF330AZ2Request a Quote1093345.53.163.8577865
RCUF350AZ2Request a Quote1141358.83.183.8599899
RCUF380AZ2Request a Quote1256396.83.173.8662994
RCUF400AZ2Request a Quote1304410.13.183.86851027
RCUF450AZ2Request a Quote1467461.33.183.87701156
RCUF500AZ2Request a Quote1630512.63.183.88561284
RCUF550AZ2Request a Quote1793563.83.183.89411412
RCUF600AZ2Request a Quote1956615.13.183.810271540
  • Cooling: leaving water 7 °C; water flow 0.172 m³/(h·kW); outdoor air 35 °C dry bulb. Water-side fouling factor: 0.018 m²·°C/kW.
  • R134a; main supply 380 V / 3 phase / 50 Hz; control supply 220 V / 1 phase / 50 Hz. Project duty, ambient conditions, electrical arrangements and water-side design pressure need a final equipment selection.
  • CSPF is the printed seasonal metric; it is not instantaneous COP or a promised project saving.
  • Cooling envelope: leaving water 5–20 °C; outdoor air 5–43 °C.
  • Source: AZ2 / AZP2 / AZX brochure, print code Z0050044-260608.

AZ2 / RCUF — water-side and installation data

Net, shipping and operating weights are separate source fields; circuit pressure drops are not summed.

AZ2 / RCUF — water-side and installation data. Net, shipping and operating weights are separate source fields; circuit pressure drops are not summed.
Model referenceWater flow(m³/h)Water pressure drop by circuit (kPa)Length(mm)Width(mm)Height(mm)Net weight(kg)Shipping weight(kg)Operating weight(kg)
RCUF150AZ2Request a Quote84.133630020522405504050605340
RCUF180AZ2Request a Quote103.938630020522405541054305670
RCUF200AZ2Request a Quote112.143630020522405560056205860
RCUF300AZ2Request a Quote168.233/331270020522405100801012010680
RCUF330AZ2Request a Quote18838/331270020522405104501049011010
RCUF350AZ2Request a Quote196.343/331270020522405106401068011200
RCUF380AZ2Request a Quote21643/381270020522405110101105011530
RCUF400AZ2Request a Quote224.343/431270020522405112001124011720
RCUF450AZ2Request a Quote252.333/33/331910020522405151201518016020
RCUF500AZ2Request a Quote280.443/33/331910020522405156801574016540
RCUF550AZ2Request a Quote308.443/43/331910020522405162401630017060
RCUF600AZ2Request a Quote336.443/43/431910020522405168001686017580
  • Cooling: leaving water 7 °C; water flow 0.172 m³/(h·kW); outdoor air 35 °C dry bulb. Water-side fouling factor: 0.018 m²·°C/kW.
  • R134a; main supply 380 V / 3 phase / 50 Hz; control supply 220 V / 1 phase / 50 Hz. Project duty, ambient conditions, electrical arrangements and water-side design pressure need a final equipment selection.
  • CSPF is the printed seasonal metric; it is not instantaneous COP or a promised project saving.
  • Cooling envelope: leaving water 5–20 °C; outdoor air 5–43 °C.
  • Source: AZ2 / AZP2 / AZX brochure, print code Z0050044-260608.

AZ2 / RHUF — cooling and heating performance

Fixed-speed semi-hermetic twin-screw heat pumps. RCUF and RHUF are separate model selections.

AZ2 / RHUF — cooling and heating performance. Fixed-speed semi-hermetic twin-screw heat pumps. RCUF and RHUF are separate model selections.
Model referenceCooling capacity(kW)Cooling input power(kW)Cooling COP(W/W)CSPF(dimensionless)Heating capacity(kW)Heating input power(kW)Heating COP(W/W)Cooling rated current(A)Cooling maximum current(A)
RHUF150AZ2Request a Quote489153.83.183.8474142.73.32257385
RHUF180AZ2Request a Quote604191.73.153.8571175.53.25320480
RHUF200AZ2Request a Quote6522053.183.8632188.43.35342513
RHUF300AZ2Request a Quote978307.53.183.8948285.43.32514770
RHUF330AZ2Request a Quote1093345.53.163.81045318.23.28577865
RHUF350AZ2Request a Quote1141358.83.183.81106331.13.34599899
RHUF380AZ2Request a Quote1256396.83.173.81203363.93.31662994
RHUF400AZ2Request a Quote1304410.13.183.81264376.83.356851027
RHUF450AZ2Request a Quote1467461.33.183.81422428.13.327701156
RHUF500AZ2Request a Quote1630512.63.183.81580473.83.338561284
RHUF550AZ2Request a Quote1793563.83.183.81738519.53.359411412
RHUF600AZ2Request a Quote1956615.13.183.81896565.23.3510271540
  • Cooling: leaving water 7 °C; water flow 0.172 m³/(h·kW); outdoor air 35 °C dry bulb. Water-side fouling factor: 0.018 m²·°C/kW.
  • R134a; main supply 380 V / 3 phase / 50 Hz; control supply 220 V / 1 phase / 50 Hz. Project duty, ambient conditions, electrical arrangements and water-side design pressure need a final equipment selection.
  • Heating: leaving water 45 °C; water flow 0.172 m³/(h·kW); outdoor air 7 °C dry bulb / 6 °C wet bulb. These are separate heating ratings, not an extension of the cooling test point.
  • CSPF is the printed seasonal metric; it is not instantaneous COP or a promised project saving.
  • Cooling envelope: leaving water 5–20 °C; outdoor air 5–43 °C. Heating envelope: leaving water 35–60 °C; outdoor air −10–21 °C.
  • Source: AZ2 / AZP2 / AZX brochure, print code Z0050044-260608.

AZ2 / RHUF — water-side and installation data

Net, shipping and operating weights are separate source fields; circuit pressure drops are not summed.

AZ2 / RHUF — water-side and installation data. Net, shipping and operating weights are separate source fields; circuit pressure drops are not summed.
Model referenceWater flow(m³/h)Water pressure drop by circuit (kPa)Length(mm)Width(mm)Height(mm)Net weight(kg)Shipping weight(kg)Operating weight(kg)
RHUF150AZ2Request a Quote84.133630020522405559056105890
RHUF180AZ2Request a Quote103.938630020522405606060806320
RHUF200AZ2Request a Quote112.143630020522405615061706410
RHUF300AZ2Request a Quote168.233/331270020522405111801122011780
RHUF330AZ2Request a Quote18838/331270020522405116501169012210
RHUF350AZ2Request a Quote196.343/331270020522405117401178012300
RHUF380AZ2Request a Quote21643/381270020522405122101225012730
RHUF400AZ2Request a Quote224.343/431270020522405123001234012820
RHUF450AZ2Request a Quote252.333/33/331910020522405167701683017670
RHUF500AZ2Request a Quote280.443/33/331910020522405173301739018190
RHUF550AZ2Request a Quote308.443/43/331910020522405178901795018710
RHUF600AZ2Request a Quote336.443/43/431910020522405184501851019230
  • Cooling: leaving water 7 °C; water flow 0.172 m³/(h·kW); outdoor air 35 °C dry bulb. Water-side fouling factor: 0.018 m²·°C/kW.
  • R134a; main supply 380 V / 3 phase / 50 Hz; control supply 220 V / 1 phase / 50 Hz. Project duty, ambient conditions, electrical arrangements and water-side design pressure need a final equipment selection.
  • Heating: leaving water 45 °C; water flow 0.172 m³/(h·kW); outdoor air 7 °C dry bulb / 6 °C wet bulb. These are separate heating ratings, not an extension of the cooling test point.
  • CSPF is the printed seasonal metric; it is not instantaneous COP or a promised project saving.
  • Cooling envelope: leaving water 5–20 °C; outdoor air 5–43 °C. Heating envelope: leaving water 35–60 °C; outdoor air −10–21 °C.
  • Source: AZ2 / AZP2 / AZX brochure, print code Z0050044-260608.

AZP2 / RCUF — cooling-only performance

Fixed-speed semi-hermetic twin-screw chillers. RCUF and RHUF are separate model selections.

AZP2 / RCUF — cooling-only performance. Fixed-speed semi-hermetic twin-screw chillers. RCUF and RHUF are separate model selections.
Model referenceCooling capacity(kW)Cooling input power(kW)Cooling COP(W/W)CSPF(dimensionless)Cooling rated current(A)Cooling maximum current(A)
RCUF150AZP2Request a Quote502153.13.284.1256383
RCUF180AZP2Request a Quote620187.93.34.1314471
RCUF200AZP2Request a Quote669202.73.34.1338508
RCUF300AZP2Request a Quote1004306.23.284.1511767
RCUF330AZP2Request a Quote11223413.294.1569854
RCUF350AZP2Request a Quote1171355.83.294.1594891
RCUF380AZP2Request a Quote1289390.63.34.1652978
RCUF400AZP2Request a Quote1338405.43.34.16771015
RCUF450AZP2Request a Quote1506459.33.284.17671150
RCUF500AZP2Request a Quote1673508.93.294.18501275
RCUF550AZP2Request a Quote1840558.53.294.19331399
RCUF600AZP2Request a QuotePending confirmation608.13.34.110151523
  • Cooling: leaving water 7 °C; water flow 0.172 m³/(h·kW); outdoor air 35 °C dry bulb. Water-side fouling factor: 0.018 m²·°C/kW.
  • R134a; main supply 380 V / 3 phase / 50 Hz; control supply 220 V / 1 phase / 50 Hz. Project duty, ambient conditions, electrical arrangements and water-side design pressure need a final equipment selection.
  • CSPF is the printed seasonal metric; it is not instantaneous COP or a promised project saving.
  • Cooling envelope: leaving water 5–20 °C; outdoor air 5–43 °C.
  • Source: AZ2 / AZP2 / AZX brochure, print code Z0050044-260608.
  • Cooling capacity for RCUF600AZP2 requires manufacturer clarification and is shown as Pending confirmation. Its other printed performance and installation values are retained separately.

AZP2 / RCUF — water-side and installation data

Net, shipping and operating weights are separate source fields; circuit pressure drops are not summed.

AZP2 / RCUF — water-side and installation data. Net, shipping and operating weights are separate source fields; circuit pressure drops are not summed.
Model referenceWater flow(m³/h)Water pressure drop by circuit (kPa)Length(mm)Width(mm)Height(mm)Net weight(kg)Shipping weight(kg)Operating weight(kg)
RCUF150AZP2Request a Quote86.335630020522456510051205400
RCUF180AZP2Request a Quote106.640630020522456561056305870
RCUF200AZP2Request a Quote115.145630020522456570057205960
RCUF300AZP2Request a Quote172.735/351270020522456102001024010800
RCUF330AZP2Request a Quote19340/351270020522456107101075011270
RCUF350AZP2Request a Quote201.445/351270020522456108001084011360
RCUF380AZP2Request a Quote221.745/401270020522456113101135011830
RCUF400AZP2Request a Quote230.145/451270020522456114001144011920
RCUF450AZP2Request a Quote25935/35/351910020522456153001536016200
RCUF500AZP2Request a Quote287.845/35/351910020522456159001596016760
RCUF550AZP2Request a Quote316.545/45/351910020522456165001656017320
RCUF600AZP2Request a Quote345.245/45/451910020522456171001716017880
  • Cooling: leaving water 7 °C; water flow 0.172 m³/(h·kW); outdoor air 35 °C dry bulb. Water-side fouling factor: 0.018 m²·°C/kW.
  • R134a; main supply 380 V / 3 phase / 50 Hz; control supply 220 V / 1 phase / 50 Hz. Project duty, ambient conditions, electrical arrangements and water-side design pressure need a final equipment selection.
  • CSPF is the printed seasonal metric; it is not instantaneous COP or a promised project saving.
  • Cooling envelope: leaving water 5–20 °C; outdoor air 5–43 °C.
  • Source: AZ2 / AZP2 / AZX brochure, print code Z0050044-260608.
  • Cooling capacity for RCUF600AZP2 requires manufacturer clarification and is shown as Pending confirmation. Its other printed performance and installation values are retained separately.

AZP2 / RHUF — cooling and heating performance

Fixed-speed semi-hermetic twin-screw heat pumps. RCUF and RHUF are separate model selections.

AZP2 / RHUF — cooling and heating performance. Fixed-speed semi-hermetic twin-screw heat pumps. RCUF and RHUF are separate model selections.
Model referenceCooling capacity(kW)Cooling input power(kW)Cooling COP(W/W)CSPF(dimensionless)Heating capacity(kW)Heating input power(kW)Heating COP(W/W)Cooling rated current(A)Cooling maximum current(A)
RHUF150AZP2Request a Quote502153.13.284.1488142.73.42256383
RHUF180AZP2Request a Quote620187.93.34.1588175.53.35314471
RHUF200AZP2Request a Quote669202.73.34.1650188.43.45338508
RHUF300AZP2Request a Quote1004306.23.284.1976285.43.42511767
RHUF330AZP2Request a Quote11223413.294.11076318.23.38569854
RHUF350AZP2Request a Quote1171355.83.294.11138331.13.44594891
RHUF380AZP2Request a Quote1289390.63.34.11238363.93.4652978
RHUF400AZP2Request a Quote1338405.43.34.11300376.83.456771015
RHUF450AZP2Request a Quote1506459.33.284.11464428.13.427671150
RHUF500AZP2Request a Quote1673508.93.294.11626473.83.438501275
RHUF550AZP2Request a Quote1840558.53.294.11788519.53.449331399
RHUF600AZP2Request a Quote2007608.13.34.11950565.23.4510151523
  • Cooling: leaving water 7 °C; water flow 0.172 m³/(h·kW); outdoor air 35 °C dry bulb. Water-side fouling factor: 0.018 m²·°C/kW.
  • R134a; main supply 380 V / 3 phase / 50 Hz; control supply 220 V / 1 phase / 50 Hz. Project duty, ambient conditions, electrical arrangements and water-side design pressure need a final equipment selection.
  • Heating: leaving water 45 °C; water flow 0.172 m³/(h·kW); outdoor air 7 °C dry bulb / 6 °C wet bulb. These are separate heating ratings, not an extension of the cooling test point.
  • CSPF is the printed seasonal metric; it is not instantaneous COP or a promised project saving.
  • Cooling envelope: leaving water 5–20 °C; outdoor air 5–43 °C. Heating envelope: leaving water 35–60 °C; outdoor air −10–21 °C.
  • Source: AZ2 / AZP2 / AZX brochure, print code Z0050044-260608.

AZP2 / RHUF — water-side and installation data

Net, shipping and operating weights are separate source fields; circuit pressure drops are not summed.

AZP2 / RHUF — water-side and installation data. Net, shipping and operating weights are separate source fields; circuit pressure drops are not summed.
Model referenceWater flow(m³/h)Water pressure drop by circuit (kPa)Length(mm)Width(mm)Height(mm)Net weight(kg)Shipping weight(kg)Operating weight(kg)
RHUF150AZP2Request a Quote86.335630020522456565056705950
RHUF180AZP2Request a Quote106.640630020522456616061806420
RHUF200AZP2Request a Quote115.145630020522456625062706510
RHUF300AZP2Request a Quote172.735/351270020522456113001134011900
RHUF330AZP2Request a Quote19340/351270020522456118101185012370
RHUF350AZP2Request a Quote201.445/351270020522456119001194012460
RHUF380AZP2Request a Quote221.745/401270020522456124101245012930
RHUF400AZP2Request a Quote230.145/451270020522456125001254013020
RHUF450AZP2Request a Quote25935/35/351910020522456169501701017850
RHUF500AZP2Request a Quote287.845/35/351910020522456175501761018410
RHUF550AZP2Request a Quote316.545/45/351910020522456181501821018970
RHUF600AZP2Request a Quote345.245/45/451910020522456187501881019530
  • Cooling: leaving water 7 °C; water flow 0.172 m³/(h·kW); outdoor air 35 °C dry bulb. Water-side fouling factor: 0.018 m²·°C/kW.
  • R134a; main supply 380 V / 3 phase / 50 Hz; control supply 220 V / 1 phase / 50 Hz. Project duty, ambient conditions, electrical arrangements and water-side design pressure need a final equipment selection.
  • Heating: leaving water 45 °C; water flow 0.172 m³/(h·kW); outdoor air 7 °C dry bulb / 6 °C wet bulb. These are separate heating ratings, not an extension of the cooling test point.
  • CSPF is the printed seasonal metric; it is not instantaneous COP or a promised project saving.
  • Cooling envelope: leaving water 5–20 °C; outdoor air 5–43 °C. Heating envelope: leaving water 35–60 °C; outdoor air −10–21 °C.
  • Source: AZ2 / AZP2 / AZX brochure, print code Z0050044-260608.

AZX / RCUF — cooling-only performance

Fixed-speed semi-hermetic twin-screw chillers. RCUF and RHUF are separate model selections.

AZX / RCUF — cooling-only performance. Fixed-speed semi-hermetic twin-screw chillers. RCUF and RHUF are separate model selections.
Model referenceCooling capacity(kW)Cooling input power(kW)Cooling COP(W/W)CSPF(dimensionless)Cooling rated current(A)Cooling maximum current(A)
RCUF150AZXRequest a Quote524144.73.624.13242362
RCUF180AZXRequest a Quote645179.63.594.1300450
RCUF200AZXRequest a Quote696193.33.64.13323484
RCUF300AZXRequest a Quote1048289.43.624.13483725
RCUF330AZXRequest a Quote1169324.33.64.12541812
RCUF350AZXRequest a Quote12203383.614.13564847
RCUF380AZXRequest a Quote1341372.93.64.12623934
RCUF400AZXRequest a Quote1392386.63.64.13645968
RCUF450AZXRequest a Quote1572434.13.624.137251087
RCUF500AZXRequest a Quote1744482.73.614.128061209
RCUF550AZXRequest a Quote1916531.33.614.138871331
RCUF600AZXRequest a Quote2088579.93.64.139681452
  • Cooling: leaving water 7 °C; water flow 0.172 m³/(h·kW); outdoor air 35 °C dry bulb. Water-side fouling factor: 0.018 m²·°C/kW.
  • R134a; main supply 380 V / 3 phase / 50 Hz; control supply 220 V / 1 phase / 50 Hz. Project duty, ambient conditions, electrical arrangements and water-side design pressure need a final equipment selection.
  • CSPF is the printed seasonal metric; it is not instantaneous COP or a promised project saving.
  • Cooling envelope: leaving water 5–20 °C; outdoor air 5–50 °C.
  • Source: AZ2 / AZP2 / AZX brochure, print code Z0050044-260608.

AZX / RCUF — water-side and installation data

Net, shipping and operating weights are separate source fields; circuit pressure drops are not summed.

AZX / RCUF — water-side and installation data. Net, shipping and operating weights are separate source fields; circuit pressure drops are not summed.
Model referenceWater flow(m³/h)Water pressure drop by circuit (kPa)Length(mm)Width(mm)Height(mm)Net weight(kg)Shipping weight(kg)Operating weight(kg)
RCUF150AZXRequest a Quote90.135615022322630595059606210
RCUF180AZXRequest a Quote110.925690022322630706070707370
RCUF200AZXRequest a Quote119.725690022322630715071607460
RCUF300AZXRequest a Quote180.335/351240022322630119001192012420
RCUF330AZXRequest a Quote201.135/251315022322630130101303013580
RCUF350AZXRequest a Quote209.835/251315022322630131001312013670
RCUF380AZXRequest a Quote230.725/251390022322630142101423014830
RCUF400AZXRequest a Quote239.425/251390022322630143001432014920
RCUF450AZXRequest a Quote270.435/35/351865022322630178501788018630
RCUF500AZXRequest a Quote30035/35/251940022322630190501908019880
RCUF550AZXRequest a Quote329.635/25/252015022322630202502028021130
RCUF600AZXRequest a Quote359.125/25/252090022322630214502148022380
  • Cooling: leaving water 7 °C; water flow 0.172 m³/(h·kW); outdoor air 35 °C dry bulb. Water-side fouling factor: 0.018 m²·°C/kW.
  • R134a; main supply 380 V / 3 phase / 50 Hz; control supply 220 V / 1 phase / 50 Hz. Project duty, ambient conditions, electrical arrangements and water-side design pressure need a final equipment selection.
  • CSPF is the printed seasonal metric; it is not instantaneous COP or a promised project saving.
  • Cooling envelope: leaving water 5–20 °C; outdoor air 5–50 °C.
  • Source: AZ2 / AZP2 / AZX brochure, print code Z0050044-260608.

AZX / RHUF — cooling and heating performance

Fixed-speed semi-hermetic twin-screw heat pumps. RCUF and RHUF are separate model selections.

AZX / RHUF — cooling and heating performance. Fixed-speed semi-hermetic twin-screw heat pumps. RCUF and RHUF are separate model selections.
Model referenceCooling capacity(kW)Cooling input power(kW)Cooling COP(W/W)CSPF(dimensionless)Heating capacity(kW)Heating input power(kW)Heating COP(W/W)Cooling rated current(A)Cooling maximum current(A)
RHUF150AZXRequest a Quote524144.73.624.13512140.33.65242362
RHUF180AZXRequest a Quote645179.63.594.16131793.42300450
RHUF200AZXRequest a Quote696193.33.64.136821993.43323484
RHUF300AZXRequest a Quote1048289.43.624.131024280.53.65483725
RHUF330AZXRequest a Quote1169324.33.64.121125319.33.52541812
RHUF350AZXRequest a Quote12203383.614.131194339.33.52564847
RHUF380AZXRequest a Quote1341372.93.64.1212953783.43623934
RHUF400AZXRequest a Quote1392386.63.64.1313643983.43645968
RHUF450AZXRequest a Quote1572434.13.624.131536420.83.657251087
RHUF500AZXRequest a Quote1744482.73.614.121706479.53.568061209
RHUF550AZXRequest a Quote1916531.33.614.131876538.33.498871331
RHUF600AZXRequest a Quote2088579.93.64.1320465973.439681452
  • Cooling: leaving water 7 °C; water flow 0.172 m³/(h·kW); outdoor air 35 °C dry bulb. Water-side fouling factor: 0.018 m²·°C/kW.
  • R134a; main supply 380 V / 3 phase / 50 Hz; control supply 220 V / 1 phase / 50 Hz. Project duty, ambient conditions, electrical arrangements and water-side design pressure need a final equipment selection.
  • Heating: leaving water 45 °C; water flow 0.172 m³/(h·kW); outdoor air 7 °C dry bulb / 6 °C wet bulb. These are separate heating ratings, not an extension of the cooling test point.
  • CSPF is the printed seasonal metric; it is not instantaneous COP or a promised project saving.
  • Cooling envelope: leaving water 5–20 °C; outdoor air 5–50 °C. Heating envelope: leaving water 35–60 °C; outdoor air −10–21 °C.
  • Source: AZ2 / AZP2 / AZX brochure, print code Z0050044-260608.

AZX / RHUF — water-side and installation data

Net, shipping and operating weights are separate source fields; circuit pressure drops are not summed.

AZX / RHUF — water-side and installation data. Net, shipping and operating weights are separate source fields; circuit pressure drops are not summed.
Model referenceWater flow(m³/h)Water pressure drop by circuit (kPa)Length(mm)Width(mm)Height(mm)Net weight(kg)Shipping weight(kg)Operating weight(kg)
RHUF150AZXRequest a Quote90.135615022322630650065106760
RHUF180AZXRequest a Quote110.925690022322630761076207920
RHUF200AZXRequest a Quote119.725690022322630770077108010
RHUF300AZXRequest a Quote180.335/351240022322630130001302013520
RHUF330AZXRequest a Quote201.135/251315022322630141101413014680
RHUF350AZXRequest a Quote209.835/251315022322630142001422014770
RHUF380AZXRequest a Quote230.725/251390022322630153101533015930
RHUF400AZXRequest a Quote239.425/251390022322630154001542016020
RHUF450AZXRequest a Quote270.435/35/351865022322630195001953020280
RHUF500AZXRequest a Quote30035/35/251940022322630207002073021530
RHUF550AZXRequest a Quote329.635/25/252015022322630219002193022780
RHUF600AZXRequest a Quote359.125/25/252090022322630231002313024030
  • Cooling: leaving water 7 °C; water flow 0.172 m³/(h·kW); outdoor air 35 °C dry bulb. Water-side fouling factor: 0.018 m²·°C/kW.
  • R134a; main supply 380 V / 3 phase / 50 Hz; control supply 220 V / 1 phase / 50 Hz. Project duty, ambient conditions, electrical arrangements and water-side design pressure need a final equipment selection.
  • Heating: leaving water 45 °C; water flow 0.172 m³/(h·kW); outdoor air 7 °C dry bulb / 6 °C wet bulb. These are separate heating ratings, not an extension of the cooling test point.
  • CSPF is the printed seasonal metric; it is not instantaneous COP or a promised project saving.
  • Cooling envelope: leaving water 5–20 °C; outdoor air 5–50 °C. Heating envelope: leaving water 35–60 °C; outdoor air −10–21 °C.
  • Source: AZ2 / AZP2 / AZX brochure, print code Z0050044-260608.

Key configuration options

  • Choose the subseries and cooling-only RCUF or heat-pump RHUF configuration before comparing performance.
  • Semi-hermetic twin-screw compressors with star-delta starting. Source main supply is 380 V / 3 phase / 50 Hz; control supply is 220 V / 1 phase / 50 Hz.
  • AZX 180 and 200 references use a flooded water-side heat exchanger; the other listed AZX sizes use the separate dry-expansion arrangement. Do not generalize one construction to every size.
  • Manufacturer reference: AZ2 / AZP2 / AZX brochure, print code Z0050044-260608. RCUF600AZP2 cooling capacity awaits manufacturer clarification; its other printed values remain listed.

Applications

  • Outdoor chilled-water systems for commercial and industrial projects.
  • Cooling and, for the listed RHUF models, heating equipment selected for the project's design conditions.

Information for equipment selection

  • RCUF cooling-only or RHUF heat-pump duty, complete model reference and quantity.
  • Cooling and heating loads, water temperatures / flow and design outdoor dry-bulb / wet-bulb conditions.
  • Power supply, outdoor installation space, access and water-side design pressure.
  • Equipment schedule or BOQ, destination country and requested delivery date.

Application suitability requires a review of the project requirements and selected model.

Project equipment procurement

Delta M&E reviews equipment requirements, manufacturer selections and supply arrangements for each inquiry. Send your BOQ or equipment schedule to discuss the required model, documentation and destination.

Technical documents

No model-specific technical documents are available for download on this page. Request Technical Information

Related series

REQUEST A QUOTE / TECHNICAL INFORMATION

Prepare your equipment requirements

Product reference: Hitachi AZ2 / AZP2 / AZX Air-Cooled Screw Chillers & Heat Pumps

Prepare your BOQ or model list, quantity, project location, design conditions and power supply. For stock inquiries, confirm the exact model, condition, export suitability and delivery requirements.

Request a Quote

Email your requirements to [email protected]. You can include your BOQ or equipment schedule. See what to include in your inquiry.