Hitachi Cooling & Heating / SERIES OVERVIEW

Hitachi S Series Water-Cooled Centrifugal Chillers

Water-cooled, geared centrifugal chiller

Brand
Hitachi Cooling & Heating
Series
S
Equipment category
Chillers

Product overview

S-series centrifugal equipment uses a geared, two-stage compression arrangement. The cooling tables distinguish GXG and GFG selections at 380 V from GXGH and GFGH high-voltage selections at 10 kV. The 50 complete R134a examples span 350 to 3,000 USRT. Compressor, heat exchanger, voltage and starting configuration remain tied to each reference; the cooling ratings below are for conventional chilled-water duty.

Key technical specifications

Match the complete model and configuration to your design duty. Compare ratings only at the stated water and ambient conditions; then send the model reference, quantity and project requirements for review.

Scroll each table horizontally to compare all columns. Model references remain visible as you scroll.

S / GXG — cooling performance

S / GXG. 380 V / 3 phase / 3 wire / 50 Hz; star-delta starting. R134a. Each complete reference includes its compressor and heat-exchanger selection.

S / GXG — cooling performance. S / GXG. 380 V / 3 phase / 3 wire / 50 Hz; star-delta starting. R134a. Each complete reference includes its compressor and heat-exchanger selection.
Model referenceCooling capacity (source)(USRT)Cooling capacity(kW)Cooling input power(kW)Full-load input / ton(kW/TR)Cooling COP(W/W)Rated current(A)Starting current(A)
HC-F05-L35EA03SCA08-GXG-SSCRequest a Quote3501231210.90.6035.836355557
HC-F10-L35EB05SCB08-GXG-SSCRequest a Quote4501582270.90.6025.841455764
HC-F20-L35EC09SCC01-GXG-SSCRequest a Quote5501934328.10.5975.894552988
HC-F20-L35EC11SCC07-GXG-SSCRequest a Quote65022863870.5955.9066521159
HC-F25-L35ED10SCE09-GXG-SSCRequest a Quote75026374480.5975.8877561052
HC-F25-L35ED03SCE07-GXG-SSCRequest a Quote8502989505.60.5955.9118541052
HC-F30-L35EE04SCM08-GXG-SSCRequest a Quote9503340565.10.5955.9119601590
HC-F30-L35EE03SCM04-GXG-SSCRequest a Quote10503692624.10.5945.91610491846
HC-F30-L35EE09SCM09-GXG-SSCRequest a Quote11003868653.30.5945.92110981846
HC-F35-L35EF03SCN10-GXG-SSCRequest a Quote12004220713.70.5955.91211972384
HC-F35-L35EF09SCN05-GXG-SSCRequest a Quote13004571773.20.5955.91212972384
HC-F35-L35EF05SCN11-GXG-SSCRequest a Quote14004923833.80.5965.90413982384
  • Cooling rating: chilled water entering / leaving 12 / 7 °C; condenser water entering / leaving 32 / 37 °C. Water-side fouling factors: evaporator 0.018 m²·°C/kW; condenser 0.044 m²·°C/kW. Capacities in USRT and kW, input power, COP and kW/TR are the independently printed values, not recalculated conversions. IPLV.SI, where listed, is a separate part-load index.
  • Main supply: 380 V / 3 phase / 3 wire / 50 Hz; star-delta starting. R134a references only. Net and operating weights remain in the source unit t (tonnes).
  • These are manufacturer selection examples. Confirm the full model, water conditions, electrical configuration, plant-room access and destination requirements for the equipment quotation.

S / GXG — water-side and installation data

S / GXG. 380 V / 3 phase / 3 wire / 50 Hz; star-delta starting. R134a. Each complete reference includes its compressor and heat-exchanger selection.

S / GXG — water-side and installation data. S / GXG. 380 V / 3 phase / 3 wire / 50 Hz; star-delta starting. R134a. Each complete reference includes its compressor and heat-exchanger selection.
Model referenceEvaporator water flow(m³/h)Evaporator pressure drop(kPa)Evaporator connectionCondenser water flow(m³/h)Condenser pressure drop(kPa)Condenser connectionLength(mm)Width(mm)Height(mm)Net weight(t)Operating weight(t)
HC-F05-L35EA03SCA08-GXG-SSCRequest a Quote211.771.3DN20024864.3DN2004100165022006.88.1
HC-F10-L35EB05SCB08-GXG-SSCRequest a Quote272.268.1DN200318.760.2DN2004150190024007.59
HC-F20-L35EC09SCC01-GXG-SSCRequest a Quote332.669.7DN200389.162.1DN2504150200024508.710.5
HC-F20-L35EC11SCC07-GXG-SSCRequest a Quote393.170.8DN250459.761.7DN250415020002450910.9
HC-F25-L35ED10SCE09-GXG-SSCRequest a Quote453.671.7DN250530.764.9DN25042002350275010.512.6
HC-F25-L35ED03SCE07-GXG-SSCRequest a Quote514.172.3DN250601.161DN30042002350275010.913.2
HC-F30-L35EE04SCM08-GXG-SSCRequest a Quote574.673.3DN300671.862.1DN30042002500290012.815.3
HC-F30-L35EE03SCM04-GXG-SSCRequest a Quote63572.1DN300742.464.2DN35042002500290013.315.9
HC-F30-L35EE09SCM09-GXG-SSCRequest a Quote665.371.5DN300777.663.5DN35042002500290013.516.2
HC-F35-L35EF03SCN10-GXG-SSCRequest a Quote725.867.1DN300848.562.3DN35042002650295014.217.5
HC-F35-L35EF09SCN05-GXG-SSCRequest a Quote786.270.8DN350919.265.4DN40042002650295014.417.8
HC-F35-L35EF05SCN11-GXG-SSCRequest a Quote846.771.3DN350990.169.6DN40042002650295014.618.1
  • Cooling rating: chilled water entering / leaving 12 / 7 °C; condenser water entering / leaving 32 / 37 °C. Water-side fouling factors: evaporator 0.018 m²·°C/kW; condenser 0.044 m²·°C/kW. Capacities in USRT and kW, input power, COP and kW/TR are the independently printed values, not recalculated conversions. IPLV.SI, where listed, is a separate part-load index.
  • Main supply: 380 V / 3 phase / 3 wire / 50 Hz; star-delta starting. R134a references only. Net and operating weights remain in the source unit t (tonnes).
  • These are manufacturer selection examples. Confirm the full model, water conditions, electrical configuration, plant-room access and destination requirements for the equipment quotation.

S / GXGH — cooling performance

S / GXGH. 10 kV / 3 phase / 3 wire / 50 Hz; reactor starting. R134a. Each complete reference includes its compressor and heat-exchanger selection.

S / GXGH — cooling performance. S / GXGH. 10 kV / 3 phase / 3 wire / 50 Hz; reactor starting. R134a. Each complete reference includes its compressor and heat-exchanger selection.
Model referenceCooling capacity (source)(USRT)Cooling capacity(kW)Cooling input power(kW)Full-load input / ton(kW/TR)Cooling COP(W/W)Rated current(A)Starting current(A)
HC-F20-L35EC09SCC01-GXGH-SSCRequest a Quote5501934331.30.6025.8372284
HC-F20-L35EC11SCC07-GXGH-SSCRequest a Quote6502286390.80.6015.8482684
HC-F25-L35ED10SCE09-GXGH-SSCRequest a Quote7502637452.50.6035.8283184
HC-F25-L35ED03SCE07-GXGH-SSCRequest a Quote8502989510.70.6015.85334101
HC-F30-L35EE04SCM08-GXGH-SSCRequest a Quote9503340570.70.6015.85337125
HC-F30-L35EE03SCM04-GXGH-SSCRequest a Quote10503692630.40.65.85742151
HC-F30-L35EE09SCM09-GXGH-SSCRequest a Quote11003868659.90.65.86144151
HC-F35-L35EF03SCN10-GXGH-SSCRequest a Quote12004220720.90.6015.85348165
HC-F35-L35EF09SCN05-GXGH-SSCRequest a Quote13004571781.10.6015.85252165
HC-F35-L35EF05SCN11-GXGH-SSCRequest a Quote14004923842.40.6025.84456165
HC-F40-L35EG02SCG10-GXGH-SSCRequest a Quote15005274885.70.595.95558185
HC-F40-L35EG04SCG06-GXGH-SSCRequest a Quote160056269440.595.9662185
HC-F40A-L35EH05SCH07-GXGH-SSCRequest a Quote1800632910620.595.9667220
  • Cooling rating: chilled water entering / leaving 12 / 7 °C; condenser water entering / leaving 32 / 37 °C. Water-side fouling factors: evaporator 0.018 m²·°C/kW; condenser 0.044 m²·°C/kW. Capacities in USRT and kW, input power, COP and kW/TR are the independently printed values, not recalculated conversions. IPLV.SI, where listed, is a separate part-load index.
  • Main supply: 10 kV / 3 phase / 3 wire / 50 Hz; reactor starting. R134a references only. Net and operating weights remain in the source unit t (tonnes).
  • These are manufacturer selection examples. Confirm the full model, water conditions, electrical configuration, plant-room access and destination requirements for the equipment quotation.

S / GXGH — water-side and installation data

S / GXGH. 10 kV / 3 phase / 3 wire / 50 Hz; reactor starting. R134a. Each complete reference includes its compressor and heat-exchanger selection.

S / GXGH — water-side and installation data. S / GXGH. 10 kV / 3 phase / 3 wire / 50 Hz; reactor starting. R134a. Each complete reference includes its compressor and heat-exchanger selection.
Model referenceEvaporator water flow(m³/h)Evaporator pressure drop(kPa)Evaporator connectionCondenser water flow(m³/h)Condenser pressure drop(kPa)Condenser connectionLength(mm)Width(mm)Height(mm)Net weight(t)Operating weight(t)
HC-F20-L35EC09SCC01-GXGH-SSCRequest a Quote332.669.7DN200389.662.3DN2504150200024508.910.7
HC-F20-L35EC11SCC07-GXGH-SSCRequest a Quote393.170.8DN250460.361.9DN2504150200024509.211.1
HC-F25-L35ED10SCE09-GXGH-SSCRequest a Quote453.671.7DN250531.465.1DN25042002350275010.712.8
HC-F25-L35ED03SCE07-GXGH-SSCRequest a Quote514.172.3DN250601.961.1DN30042002350275011.113.4
HC-F30-L35EE04SCM08-GXGH-SSCRequest a Quote574.673.3DN300672.762.2DN30042502500290013.115.6
HC-F30-L35EE03SCM04-GXGH-SSCRequest a Quote63572.1DN300743.564.4DN35042502500290013.616.2
HC-F30-L35EE09SCM09-GXGH-SSCRequest a Quote665.371.5DN300778.863.6DN35042502500290013.816.5
HC-F35-L35EF03SCN10-GXGH-SSCRequest a Quote725.867.1DN300849.862.5DN35043002650295014.517.8
HC-F35-L35EF09SCN05-GXGH-SSCRequest a Quote786.270.8DN350920.665.6DN40043002650295014.718.1
HC-F35-L35EF05SCN11-GXGH-SSCRequest a Quote846.771.3DN350991.669.8DN40043002650295014.918.4
HC-F40-L35EG02SCG10-GXGH-SSCRequest a Quote907.270.7DN400106063.3DN4004700320034002024.1
HC-F40-L35EG04SCG06-GXGH-SSCRequest a Quote967.769.9DN400113064.7DN40047003200340020.324.5
HC-F40A-L35EH05SCH07-GXGH-SSCRequest a Quote108970.3DN400127163DN45048003350355021.225.8
  • Cooling rating: chilled water entering / leaving 12 / 7 °C; condenser water entering / leaving 32 / 37 °C. Water-side fouling factors: evaporator 0.018 m²·°C/kW; condenser 0.044 m²·°C/kW. Capacities in USRT and kW, input power, COP and kW/TR are the independently printed values, not recalculated conversions. IPLV.SI, where listed, is a separate part-load index.
  • Main supply: 10 kV / 3 phase / 3 wire / 50 Hz; reactor starting. R134a references only. Net and operating weights remain in the source unit t (tonnes).
  • These are manufacturer selection examples. Confirm the full model, water conditions, electrical configuration, plant-room access and destination requirements for the equipment quotation.

S / GFG — cooling performance

S / GFG. 380 V / 3 phase / 3 wire / 50 Hz; star-delta starting. R134a. Each complete reference includes its compressor and heat-exchanger selection.

S / GFG — cooling performance. S / GFG. 380 V / 3 phase / 3 wire / 50 Hz; star-delta starting. R134a. Each complete reference includes its compressor and heat-exchanger selection.
Model referenceCooling capacity (source)(USRT)Cooling capacity(kW)Cooling input power(kW)Full-load input / ton(kW/TR)Cooling COP(W/W)Rated current(A)Starting current(A)
HC-F05-L40EA03SCA08-GFG-SSCRequest a Quote3501231202.70.5796.073341557
HC-F10-L40EB05SCB08-GFG-SSCRequest a Quote4501582260.40.5796.075437764
HC-F20-L40EC09SCC01-GFG-SSCRequest a Quote5501934312.40.5686.19526988
HC-F20-L40EC11SCC07-GFG-SSCRequest a Quote6502286368.60.5676.2016211159
HC-F25-L40ED10SCE09-GFG-SSCRequest a Quote7502637426.80.5696.1797211052
HC-F25-L40ED03SCE07-GFG-SSCRequest a Quote8502989481.60.5676.2068131052
HC-F30-L40EE04SCM08-GFG-SSCRequest a Quote9503340544.50.5736.1359251590
HC-F30-L40EE03SCM04-GFG-SSCRequest a Quote10503692601.10.5726.14210101846
HC-F30-L40EE09SCM09-GFG-SSCRequest a Quote11003868628.80.5726.15110571846
HC-F35-L40EF03SCN10-GFG-SSCRequest a Quote12004220684.90.5716.16111492384
HC-F35-L40EF09SCN05-GFG-SSCRequest a Quote13004571741.70.5716.16312442384
HC-F35-L40EF05SCN11-GFG-SSCRequest a Quote14004923799.50.5716.15713412384
  • Cooling rating: chilled water entering / leaving 12 / 7 °C; condenser water entering / leaving 32 / 37 °C. Water-side fouling factors: evaporator 0.018 m²·°C/kW; condenser 0.044 m²·°C/kW. Capacities in USRT and kW, input power, COP and kW/TR are the independently printed values, not recalculated conversions. IPLV.SI, where listed, is a separate part-load index.
  • Main supply: 380 V / 3 phase / 3 wire / 50 Hz; star-delta starting. R134a references only. Net and operating weights remain in the source unit t (tonnes).
  • These are manufacturer selection examples. Confirm the full model, water conditions, electrical configuration, plant-room access and destination requirements for the equipment quotation.

S / GFG — water-side and installation data

S / GFG. 380 V / 3 phase / 3 wire / 50 Hz; star-delta starting. R134a. Each complete reference includes its compressor and heat-exchanger selection.

S / GFG — water-side and installation data. S / GFG. 380 V / 3 phase / 3 wire / 50 Hz; star-delta starting. R134a. Each complete reference includes its compressor and heat-exchanger selection.
Model referenceEvaporator water flow(m³/h)Evaporator pressure drop(kPa)Evaporator connectionCondenser water flow(m³/h)Condenser pressure drop(kPa)Condenser connectionLength(mm)Width(mm)Height(mm)Net weight(t)Operating weight(t)
HC-F05-L40EA03SCA08-GFG-SSCRequest a Quote211.781.4DN200246.572.7DN2004600165022007.58.9
HC-F10-L40EB05SCB08-GFG-SSCRequest a Quote272.277.9DN20031768.1DN20046501900240089.6
HC-F20-L40EC09SCC01-GFG-SSCRequest a Quote332.679.7DN200386.470.1DN2504650200024509.211.1
HC-F20-L40EC11SCC07-GFG-SSCRequest a Quote393.180.9DN250456.569.7DN2504650200024509.511.6
HC-F25-L40ED10SCE09-GFG-SSCRequest a Quote453.681.9DN25052773.3DN25047002350275011.513.8
HC-F25-L40ED03SCE07-GFG-SSCRequest a Quote514.182.7DN250596.968.8DN30047002350275011.914.4
HC-F30-L40EE04SCM08-GFG-SSCRequest a Quote574.683.8DN300668.270.2DN30047002500290013.816.5
HC-F30-L40EE03SCM04-GFG-SSCRequest a Quote63582.4DN300738.472.7DN35047002500290014.317.1
HC-F30-L40EE09SCM09-GFG-SSCRequest a Quote665.381.8DN300773.471.8DN35047002500290014.517.4
HC-F35-L40EF03SCN10-GFG-SSCRequest a Quote725.876.7DN300843.670.5DN3504550265029501619.6
HC-F35-L40EF09SCN05-GFG-SSCRequest a Quote786.281DN350913.873.9DN40045502650295016.319.9
HC-F35-L40EF05SCN11-GFG-SSCRequest a Quote846.781.5DN350984.278.7DN40045502650295016.520.3
  • Cooling rating: chilled water entering / leaving 12 / 7 °C; condenser water entering / leaving 32 / 37 °C. Water-side fouling factors: evaporator 0.018 m²·°C/kW; condenser 0.044 m²·°C/kW. Capacities in USRT and kW, input power, COP and kW/TR are the independently printed values, not recalculated conversions. IPLV.SI, where listed, is a separate part-load index.
  • Main supply: 380 V / 3 phase / 3 wire / 50 Hz; star-delta starting. R134a references only. Net and operating weights remain in the source unit t (tonnes).
  • These are manufacturer selection examples. Confirm the full model, water conditions, electrical configuration, plant-room access and destination requirements for the equipment quotation.

S / GFGH — cooling performance

S / GFGH. 10 kV / 3 phase / 3 wire / 50 Hz; reactor starting. R134a. Each complete reference includes its compressor and heat-exchanger selection.

S / GFGH — cooling performance. S / GFGH. 10 kV / 3 phase / 3 wire / 50 Hz; reactor starting. R134a. Each complete reference includes its compressor and heat-exchanger selection.
Model referenceCooling capacity (source)(USRT)Cooling capacity(kW)Cooling input power(kW)Full-load input / ton(kW/TR)Cooling COP(W/W)Rated current(A)Starting current(A)
HC-F35-L40EF05SCN11-GFGH-SSCRequest a Quote14004923807.30.5776.09854165
HC-F40-L40EG02SCG10-GFGH-SSCRequest a Quote15005274843.80.5636.25155185
HC-F40-L40EG04SCG06-GFGH-SSCRequest a Quote16005626899.30.5626.25659185
HC-F40A-L40EH05SCH07-GFGH-SSCRequest a Quote1800632910290.5726.1565220
HC-F40A-L40EH04SCH03-GFGH-SSCRequest a Quote2000703311390.576.17272220
HC-F50-L40EH05SCH07-GFGH-SSCRequest a Quote1800632910110.5626.25864220
HC-F50-L40EH04SCH03-GFGH-SSCRequest a Quote2000703311250.5636.24972252
HC-F50-L45EJ04SCJ09-GFGH-SSCRequest a Quote2200773612110.556.38677252
HC-F50-L45EJ06SCJ06-GFGH-SSCRequest a Quote2400843913230.5516.37886301
HC-F50-L45EJ01SCJ08-GFGH-SSCRequest a Quote2500879113760.556.38890302
HC-F50A-L45EK05SCK08-GFGH-SSCRequest a Quote2600914214440.5556.33295316
HC-F50A-L45EK08SCK01-GFGH-SSCRequest a Quote2800984615670.566.284103316
HC-F50A-L45EK02SCK02-GFGH-SSCRequest a Quote30001054916940.5656.228111367
  • Cooling rating: chilled water entering / leaving 12 / 7 °C; condenser water entering / leaving 32 / 37 °C. Water-side fouling factors: evaporator 0.018 m²·°C/kW; condenser 0.044 m²·°C/kW. Capacities in USRT and kW, input power, COP and kW/TR are the independently printed values, not recalculated conversions. IPLV.SI, where listed, is a separate part-load index.
  • Main supply: 10 kV / 3 phase / 3 wire / 50 Hz; reactor starting. R134a references only. Net and operating weights remain in the source unit t (tonnes).
  • These are manufacturer selection examples. Confirm the full model, water conditions, electrical configuration, plant-room access and destination requirements for the equipment quotation.

S / GFGH — water-side and installation data

S / GFGH. 10 kV / 3 phase / 3 wire / 50 Hz; reactor starting. R134a. Each complete reference includes its compressor and heat-exchanger selection.

S / GFGH — water-side and installation data. S / GFGH. 10 kV / 3 phase / 3 wire / 50 Hz; reactor starting. R134a. Each complete reference includes its compressor and heat-exchanger selection.
Model referenceEvaporator water flow(m³/h)Evaporator pressure drop(kPa)Evaporator connectionCondenser water flow(m³/h)Condenser pressure drop(kPa)Condenser connectionLength(mm)Width(mm)Height(mm)Net weight(t)Operating weight(t)
HC-F35-L40EF05SCN11-GFGH-SSCRequest a Quote846.781.5DN350985.678.9DN40047502650295016.820.6
HC-F40-L40EG02SCG10-GFGH-SSCRequest a Quote907.280.8DN400105271.5DN40048503200340020.525
HC-F40-L40EG04SCG06-GFGH-SSCRequest a Quote967.779.8DN400112273DN40048503200340020.825.5
HC-F40A-L40EH05SCH07-GFGH-SSCRequest a Quote108980.4DN400126671.4DN45049503350355022.227.3
HC-F40A-L40EH04SCH03-GFGH-SSCRequest a Quote121085.5DN400140676.3DN45049503350355022.627.9
HC-F50-L40EH05SCH07-GFGH-SSCRequest a Quote108980.4DN400126371.1DN4505000350037002429.1
HC-F50-L40EH04SCH03-GFGH-SSCRequest a Quote121085.5DN400140376DN45050003500370024.529.8
HC-F50-L45EJ04SCJ09-GFGH-SSCRequest a Quote133189.6DN450153981.4DN50055003750385030.237.1
HC-F50-L45EJ06SCJ06-GFGH-SSCRequest a Quote145287.8DN450167981DN5005500375038503138.2
HC-F50-L45EJ01SCJ08-GFGH-SSCRequest a Quote151286.7DN450174979.9DN50055003750385031.539
HC-F50A-L45EK05SCK08-GFGH-SSCRequest a Quote157387.2DN500182179.9DN50057003850400034.343
HC-F50A-L45EK08SCK01-GFGH-SSCRequest a Quote169388DN500196381.8DN50057003850400034.943.9
HC-F50A-L45EK02SCK02-GFGH-SSCRequest a Quote181487.9DN500210685.9DN60057003850400035.544.7
  • Cooling rating: chilled water entering / leaving 12 / 7 °C; condenser water entering / leaving 32 / 37 °C. Water-side fouling factors: evaporator 0.018 m²·°C/kW; condenser 0.044 m²·°C/kW. Capacities in USRT and kW, input power, COP and kW/TR are the independently printed values, not recalculated conversions. IPLV.SI, where listed, is a separate part-load index.
  • Main supply: 10 kV / 3 phase / 3 wire / 50 Hz; reactor starting. R134a references only. Net and operating weights remain in the source unit t (tonnes).
  • These are manufacturer selection examples. Confirm the full model, water conditions, electrical configuration, plant-room access and destination requirements for the equipment quotation.

Key configuration options

  • 380 V selections use star-delta starting; 10 kV selections use reactor starting. Both tables state 3 phase / 3 wire / 50 Hz.
  • These tables cover fixed-speed standard cooling examples. Heat-pump, ice-storage, heat-recovery and inverter options require their own duty-specific selections.
  • Provide plant-room access, lifting limits, water-side pressure requirements and selected starting arrangements for the equipment review.
  • Manufacturer reference: S brochure, print code Z0050003-251008. Other refrigerant codes in the nomenclature do not share these R134a ratings automatically.

Applications

  • Central chilled-water plants for large commercial buildings and manufacturing facilities.
  • Industrial cooling equipment procurement based on the required water temperatures, load and site conditions.

Information for equipment selection

  • Cooling duty, load profile and required quantity; complete model reference where known.
  • Chilled-water and condenser-water entering / leaving temperatures, flows and water-side pressure requirements.
  • Voltage, phase, frequency, starting method and plant-room access / lifting constraints.
  • Equipment schedule or BOQ, project location, destination country and requested delivery date.

Application suitability requires a review of the project requirements and selected model.

Project equipment procurement

Delta M&E reviews equipment requirements, manufacturer selections and supply arrangements for each inquiry. Send your BOQ or equipment schedule to discuss the required model, documentation and destination.

TCL CSOT India — historical Hitachi centrifugal chiller supply. The project record does not identify one of the series listed here.

Technical documents

No model-specific technical documents are available for download on this page. Request Technical Information

Related series

REQUEST A QUOTE / TECHNICAL INFORMATION

Prepare your equipment requirements

Product reference: Hitachi S Series Water-Cooled Centrifugal Chillers

Prepare your BOQ or model list, quantity, project location, design conditions and power supply. For stock inquiries, confirm the exact model, condition, export suitability and delivery requirements.

Request a Quote

Email your requirements to [email protected]. You can include your BOQ or equipment schedule. See what to include in your inquiry.