Product overview

VM uses magnetic bearings, a permanent-magnet motor and a direct-drive inverter centrifugal compressor. The oil-free arrangement is distinct from the oil-lubricated VG and geared S series. The tables below retain 19 R134a selection examples, from 200 to 1,100 USRT, with their complete compressor and heat-exchanger references. Final selection starts with the actual chilled-water duty and condenser-water conditions.

Key technical specifications

Match the complete model and configuration to your design duty. Compare ratings only at the stated water and ambient conditions; then send the model reference, quantity and project requirements for review.

Scroll each table horizontally to compare all columns. Model references remain visible as you scroll.

VM — cooling performance

VM. 380 V / 3 phase / 3 wire / 50 Hz; inverter starting. R134a. Each complete reference includes its compressor and heat-exchanger selection.

VM — cooling performance. VM. 380 V / 3 phase / 3 wire / 50 Hz; inverter starting. R134a. Each complete reference includes its compressor and heat-exchanger selection.
Model referenceCooling capacity (source)(USRT)Cooling capacity(kW)Cooling input power(kW)Full-load input / ton(kW/TR)Cooling COP(W/W)IPLV.SI(W/W)Rated current(A)
HC-F05PM-L35EA07SCA06-GPUVM-SCRequest a Quote200703.3129.60.6485.4279.399210
HC-F05PM-L35EA08SCA05-GPUVM-SCRequest a Quote250879.1159.70.6395.5049.526259
HC-F05PM-L35EA01SCA03-GPUVM-SCRequest a Quote3001055190.40.6355.549.59308
HC-F10PM-L35EB06SCB01-GPUVM-SCRequest a Quote3501231210.40.6015.8510.85341
HC-F10PM-L35EB02SCB04-GPUVM-SCRequest a Quote4001407240.10.65.86110.87389
HC-F10PM-L35EB05SCB02-GPUVM-SCRequest a Quote4501582270.30.6015.85310.86437
HC-F20PM-L40EC08SCC05-GPUVM-SCRequest a Quote5001758286.50.5736.13611.38464
HC-F20PM-L40EC09SCC06-GPUVM-SCRequest a Quote55019343150.5736.13911.39510
HC-F20PM-L40EC10SCC01-GPUVM-SCRequest a Quote6002110342.90.5726.15411.42555
HC-F20PM-L40EC11SCC02-GPUVM-SCRequest a Quote6502286371.30.5716.15611.42601
HC-F25PM-L40ED01SCE02-GPUVM-SCRequest a Quote7002461409.80.5856.00611.15663
HC-F25PM-L40ED10SCE05-GPUVM-SCRequest a Quote7502637438.80.5856.0111.15710
HC-F25PM-L40ED02SCE09-GPUVM-SCRequest a Quote8002813467.90.5856.01211.15757
HC-F25PM-L40ED03SCE06-GPUVM-SCRequest a Quote8502989496.90.5856.01511.16804
HC-F30PM-L40EE01SCM01-GPUVM-SCRequest a Quote9003165524.70.5836.03211.19849
HC-F30PM-L40EE04SCM07-GPUVM-SCRequest a Quote95033405530.5826.0411.21894
HC-F30PM-L40EE02SCM02-GPUVM-SCRequest a Quote10003516581.90.5826.04211.21941
HC-F30PM-L40EE03SCM08-GPUVM-SCRequest a Quote10503692610.20.5816.0511.22987
HC-F30PM-L40EE09SCM04-GPUVM-SCRequest a Quote11003868639.40.5816.04911.221034
  • Cooling rating: chilled water entering / leaving 12 / 7 °C; condenser water entering / leaving 32 / 37 °C. Water-side fouling factors: evaporator 0.018 m²·°C/kW; condenser 0.044 m²·°C/kW. Capacities in USRT and kW, input power, COP and kW/TR are the independently printed values, not recalculated conversions. IPLV.SI, where listed, is a separate part-load index.
  • Main supply: 380 V / 3 phase / 3 wire / 50 Hz; inverter starting. R134a references only. Net and operating weights remain in the source unit t (tonnes).
  • These are manufacturer selection examples. Confirm the full model, water conditions, electrical configuration, plant-room access and destination requirements for the equipment quotation.

VM — water-side and installation data

VM. 380 V / 3 phase / 3 wire / 50 Hz; inverter starting. R134a. Each complete reference includes its compressor and heat-exchanger selection.

VM — water-side and installation data. VM. 380 V / 3 phase / 3 wire / 50 Hz; inverter starting. R134a. Each complete reference includes its compressor and heat-exchanger selection.
Model referenceEvaporator water flow(m³/h)Evaporator pressure drop(kPa)Evaporator connectionCondenser water flow(m³/h)Condenser pressure drop(kPa)Condenser connectionLength(mm)Width(mm)Height(mm)Net weight(t)Operating weight(t)
HC-F05PM-L35EA07SCA06-GPUVM-SCRequest a Quote12162.6DN150142.861DN1504100200021504.96
HC-F05PM-L35EA08SCA05-GPUVM-SCRequest a Quote151.268.9DN150178.166.7DN15041002000215056.1
HC-F05PM-L35EA01SCA03-GPUVM-SCRequest a Quote181.467DN150213.671.1DN2004100200021505.16.3
HC-F10PM-L35EB06SCB01-GPUVM-SCRequest a Quote211.769.5DN200247.273DN20041502000235067.3
HC-F10PM-L35EB02SCB04-GPUVM-SCRequest a Quote241.971.4DN200282.471.9DN2004150200023506.17.5
HC-F10PM-L35EB05SCB02-GPUVM-SCRequest a Quote272.268.1DN200317.772DN2004150200023506.27.7
HC-F20PM-L40EC08SCC05-GPUVM-SCRequest a Quote302.479.7DN200350.781.7DN2504650215024007.79.5
HC-F20PM-L40EC09SCC06-GPUVM-SCRequest a Quote332.679.6DN200385.881.4DN2504650215024007.89.6
HC-F20PM-L40EC10SCC01-GPUVM-SCRequest a Quote362.980.3DN250420.781.7DN2504650215024007.99.8
HC-F20PM-L40EC11SCC02-GPUVM-SCRequest a Quote393.180.9DN250455.782.6DN250465021502400810
HC-F25PM-L40ED01SCE02-GPUVM-SCRequest a Quote423.479.4DN250492.585.2DN25047002480270010.412.6
HC-F25PM-L40ED10SCE05-GPUVM-SCRequest a Quote453.681.8DN250527.684.4DN25047002480270010.612.8
HC-F25PM-L40ED02SCE09-GPUVM-SCRequest a Quote483.882.2DN250562.782.4DN30047002480270010.813.1
HC-F25PM-L40ED03SCE06-GPUVM-SCRequest a Quote514.182.6DN250597.985.2DN3004700248027001113.3
HC-F30PM-L40EE01SCM01-GPUVM-SCRequest a Quote544.383.7DN300632.885.9DN30047002580280011.814.4
HC-F30PM-L40EE04SCM07-GPUVM-SCRequest a Quote574.683.7DN300667.884.3DN3004700258028001214.7
HC-F30PM-L40EE02SCM02-GPUVM-SCRequest a Quote604.885.4DN300702.984.4DN35047002580280012.215
HC-F30PM-L40EE03SCM08-GPUVM-SCRequest a Quote63582.3DN300737.984DN35047002580290012.715.5
HC-F30PM-L40EE09SCM04-GPUVM-SCRequest a Quote665.381.7DN300773.178.9DN35047002580290012.915.8
  • Cooling rating: chilled water entering / leaving 12 / 7 °C; condenser water entering / leaving 32 / 37 °C. Water-side fouling factors: evaporator 0.018 m²·°C/kW; condenser 0.044 m²·°C/kW. Capacities in USRT and kW, input power, COP and kW/TR are the independently printed values, not recalculated conversions. IPLV.SI, where listed, is a separate part-load index.
  • Main supply: 380 V / 3 phase / 3 wire / 50 Hz; inverter starting. R134a references only. Net and operating weights remain in the source unit t (tonnes).
  • These are manufacturer selection examples. Confirm the full model, water conditions, electrical configuration, plant-room access and destination requirements for the equipment quotation.

Key configuration options

  • R134a F-code examples only. R513A and R1234ze(E) options in the nomenclature require their own model selection and ratings.
  • Main power: 380 V / 3 phase / 3 wire / 50 Hz; control power: 220 V / 1 phase / 50 Hz. Inverter starting follows the listed configuration.
  • Select water-box arrangement, connection direction, pressure rating and plant-room access against the project schedule.
  • Manufacturer reference: VM brochure, print code Z0050001-251008. The tabulated references are selection examples, not a stock list.

Applications

  • Central chilled-water plants for large commercial buildings and manufacturing facilities.
  • Industrial cooling equipment procurement based on the required water temperatures, load and site conditions.

Information for equipment selection

  • Cooling duty, load profile and required quantity; complete model reference where known.
  • Chilled-water and condenser-water entering / leaving temperatures, flows and water-side pressure requirements.
  • Voltage, phase, frequency, starting method and plant-room access / lifting constraints.
  • Equipment schedule or BOQ, project location, destination country and requested delivery date.

Application suitability requires a review of the project requirements and selected model.

Project equipment procurement

Delta M&E reviews equipment requirements, manufacturer selections and supply arrangements for each inquiry. Send your BOQ or equipment schedule to discuss the required model, documentation and destination.

TCL CSOT India — historical Hitachi centrifugal chiller supply. The project record does not identify one of the series listed here.

Technical documents

No model-specific technical documents are available for download on this page. Request Technical Information

Related series

REQUEST A QUOTE / TECHNICAL INFORMATION

Prepare your equipment requirements

Product reference: Hitachi VM Magnetic-Bearing Centrifugal Chillers

Prepare your BOQ or model list, quantity, project location, design conditions and power supply. For stock inquiries, confirm the exact model, condition, export suitability and delivery requirements.

Request a Quote

Email your requirements to [email protected]. You can include your BOQ or equipment schedule. See what to include in your inquiry.