Hitachi Cooling & Heating / SERIES OVERVIEW

Hitachi WZP / WZ Water-Source Screw Heat Pumps

Water / ground-source twin-screw heat pump

Brand
Hitachi Cooling & Heating
Series
WZP / WZ Water-Source
Equipment category
Heat Pumps
Hitachi WZP / WZ water-source screw heat pump series

Product overview

WZP and WZ water-source heat pumps use twin-screw compressors and R134a. Their RHUF references are separate from the RCUF cooling-only chillers. This range includes standard and Q configurations with their own heating input, water flow and electrical data. Selection starts with the available source-water conditions and the required chilled-water or hot-water duty.

Key technical specifications

Match the complete model and configuration to your design duty. Compare ratings only at the stated water and ambient conditions; then send the model reference, quantity and project requirements for review.

Scroll each table horizontally to compare all columns. Model references remain visible as you scroll.

WZP — cooling and heating performance

RHUF water / ground-source screw heat-pump selections; R134a.

WZP — cooling and heating performance. RHUF water / ground-source screw heat-pump selections; R134a.
Model referenceCooling capacity(kW)Cooling input(kW)Heating capacity(kW)Heating input(kW)Capacity control (%)Maximum current(A)Starting currentCompressors(count)
RHUF50WZPRequest a Quote200.630.39179.141.8225-100129211 A1
RHUF65WZPRequest a Quote251.338.08224.452.425-100161211 A1
RHUF80WZPRequest a Quote314.747.6928165.6225-100202177/177 A2
RHUF110WZPRequest a Quote404.462.43362.785.9125-100260211/211 A2
RHUF130WZPRequest a Quote504.977.93452.7107.225-100324211/211 A2
RHUF150WZPRequest a Quote574.482.94572.7116.425-100230392 A1
RHUF156WZPRequest a Quote564.482.67565.4121.725-100230392 A1
RHUF200WZPRequest a Quote765.9110.6763.7155.225-100306509 A1
RHUF211WZPRequest a Quote752.5110.7754.6163.125-100308509 A1
RHUF250WZPRequest a Quote957.3138.2954.5193.925-100382599 A1
RHUF261WZPRequest a Quote940.7138.2942.9203.525-100384599 A1
RHUF300WZPRequest a Quote1149163.31145232.725-100460392/392 A2
RHUF311WZPRequest a Quote1129162.81144247.325-100452392/392 A2
RHUF366WZPRequest a Quote1317187.81331285.225-100522509/392 A2
RHUF421WZPRequest a Quote1505213.91521324.925-100594509/509 A2
RHUF471WZPRequest a Quote16932411711366.125-100670599/509 A2
RHUF521WZPRequest a Quote18812671900405.525-100742599/599 A2
  • Cooling: chilled water entering / leaving 12 / 7 °C; condenser water entering / leaving 25 / 30 °C. Heating: source water entering / leaving 10 / 5 °C; hot water entering / leaving 40 / 45 °C.
  • Evaporator and condenser fouling factors: 0.018 and 0.044 m²·°C/kW. Main power 380 V / 3 phase / 50 Hz; control 220 V / 1 phase / 50 Hz. R134a; twin-screw compressors.
  • Starting-current values are printed in A; slash-separated compressor values are not summed. Q selections have separate ratings and operating limits.
  • Manufacturer reference: Z0050069-260903; physical PDF page 6.

WZP — water-side and installation data

RHUF water / ground-source screw heat-pump selections; R134a.

WZP — water-side and installation data. RHUF water / ground-source screw heat-pump selections; R134a.
Model referenceChilled-water flow(m³/h)Chilled-water pressure drop(kPa)Heat-source-water flow(m³/h)Heat-source-water pressure drop(kPa)Evaporator flangeCondenser-water flow(m³/h)Condenser-water pressure drop(kPa)Hot-water flow(m³/h)Hot-water pressure drop(kPa)Condenser flangeNet weight(kg)Length(mm)Width(mm)Height(mm)
RHUF50WZPRequest a Quote34.58323.6139DN6539.735430.8133DN651800220013501600
RHUF65WZPRequest a Quote43.228429.5840DN6549.775638.634DN651880220013501600
RHUF80WZPRequest a Quote54.136537.0531DN12562.335448.3333DN1253290400013601600
RHUF110WZPRequest a Quote69.566747.6132DN12580.295562.3833DN1253450400013601600
RHUF130WZPRequest a Quote86.846959.4332DN125100.25577.8633DN1253630400013601600
RHUF150WZPRequest a Quote98.85578.4835DN150113.15498.541DN1504070337317152311
RHUF156WZPRequest a Quote97.085376.3233DN150111.37597.2557DN1503540332017002258
RHUF200WZPRequest a Quote131.755104.735DN150150.854131.441DN1504400337317152311
RHUF211WZPRequest a Quote129.453101.733DN150148.577129.859DN1503820332017002258
RHUF250WZPRequest a Quote164.755130.835DN150188.454164.241DN1504680337317152311
RHUF261WZPRequest a Quote161.853127.233DN150185.679162.261DN1504040332017002258
RHUF300WZPRequest a Quote197.664156.940DN200225.753196.941DN2008560480419492419
RHUF311WZPRequest a Quote194.271154.245DN200222.272196.857DN2006650467217662318
RHUF366WZPRequest a Quote226.573179.946DN200258.874228.958DN2006950467217662318
RHUF421WZPRequest a Quote258.975205.748DN200295.776261.660DN2007250467217662318
RHUF471WZPRequest a Quote291.277231.349DN200332.678294.361DN2007500467217662318
RHUF521WZPRequest a Quote323.580257.150DN200369.580326.863DN2007750467217662318
  • Cooling: chilled water entering / leaving 12 / 7 °C; condenser water entering / leaving 25 / 30 °C. Heating: source water entering / leaving 10 / 5 °C; hot water entering / leaving 40 / 45 °C.
  • Evaporator and condenser fouling factors: 0.018 and 0.044 m²·°C/kW. Main power 380 V / 3 phase / 50 Hz; control 220 V / 1 phase / 50 Hz. R134a; twin-screw compressors.
  • Starting-current values are printed in A; slash-separated compressor values are not summed. Q selections have separate ratings and operating limits.
  • Manufacturer reference: Z0050069-260903; physical PDF page 6.

WZP-Q — cooling and heating performance

RHUF water / ground-source screw heat-pump selections; R134a.

WZP-Q — cooling and heating performance. RHUF water / ground-source screw heat-pump selections; R134a.
Model referenceCooling capacity(kW)Cooling input(kW)Heating capacity(kW)Heating input(kW)Capacity control (%)Maximum current(A)Starting currentCompressors(count)
RHUF150WZP-QRequest a Quote574.584.58580.3118.725-100299599 A1
RHUF156WZP-QRequest a Quote564.484.21525.8123.925-100309599 A1
RHUF200WZP-QRequest a Quote766112.8773.7158.225-100398779 A1
RHUF211WZP-QRequest a Quote752.6112.8701.816625-100414779 A1
RHUF300WZP-QRequest a Quote1149166.51157233.625-100598599/599 A2
RHUF311WZP-QRequest a Quote1129165.81067251.825-100610599/599 A2
RHUF366WZP-QRequest a Quote1317191.31242290.525-100703779/599 A2
RHUF421WZP-QRequest a Quote1505217.91418330.925-100800779/779 A2
  • Cooling: chilled water entering / leaving 12 / 7 °C; condenser water entering / leaving 25 / 30 °C. Heating: source water entering / leaving 10 / 5 °C; hot water entering / leaving 40 / 45 °C.
  • Evaporator and condenser fouling factors: 0.018 and 0.044 m²·°C/kW. Main power 380 V / 3 phase / 50 Hz; control 220 V / 1 phase / 50 Hz. R134a; twin-screw compressors.
  • Starting-current values are printed in A; slash-separated compressor values are not summed. Q selections have separate ratings and operating limits.
  • Manufacturer reference: Z0050069-260903; physical PDF page 6.

WZP-Q — water-side and installation data

RHUF water / ground-source screw heat-pump selections; R134a.

WZP-Q — water-side and installation data. RHUF water / ground-source screw heat-pump selections; R134a.
Model referenceChilled-water flow(m³/h)Chilled-water pressure drop(kPa)Heat-source-water flow(m³/h)Heat-source-water pressure drop(kPa)Evaporator flangeCondenser-water flow(m³/h)Condenser-water pressure drop(kPa)Hot-water flow(m³/h)Hot-water pressure drop(kPa)Condenser flangeNet weight(kg)Length(mm)Width(mm)Height(mm)
RHUF150WZP-QRequest a Quote98.815579.435DN150113.45499.8142DN1504155337317152311
RHUF156WZP-QRequest a Quote97.085369.1327DN150111.67590.4449DN1503625332017002258
RHUF200WZP-QRequest a Quote131.855105.935DN150151.254133.142DN1504475337317152311
RHUF211WZP-QRequest a Quote129.45392.1627DN150148.877120.751DN1503895332017002258
RHUF300WZP-QRequest a Quote197.664158.841DN200226.35319941DN2008730480419492419
RHUF311WZP-QRequest a Quote194.267140.235DN200222.771183.549DN2006820467217662318
RHUF366WZP-QRequest a Quote226.573163.738DN200259.473213.650DN2007110467217662318
RHUF421WZP-QRequest a Quote258.97118737DN200296.375243.951DN2007400467217662318
  • Cooling: chilled water entering / leaving 12 / 7 °C; condenser water entering / leaving 25 / 30 °C. Heating: source water entering / leaving 10 / 5 °C; hot water entering / leaving 40 / 45 °C.
  • Evaporator and condenser fouling factors: 0.018 and 0.044 m²·°C/kW. Main power 380 V / 3 phase / 50 Hz; control 220 V / 1 phase / 50 Hz. R134a; twin-screw compressors.
  • Starting-current values are printed in A; slash-separated compressor values are not summed. Q selections have separate ratings and operating limits.
  • Manufacturer reference: Z0050069-260903; physical PDF page 6.

WZ — cooling and heating performance

RHUF water / ground-source screw heat-pump selections; R134a.

WZ — cooling and heating performance. RHUF water / ground-source screw heat-pump selections; R134a.
Model referenceCooling capacity(kW)Cooling input(kW)Heating capacity(kW)Heating input(kW)Capacity control (%)Maximum current(A)Starting currentCompressors(count)
RHUF155WZRequest a Quote564.587.11557.2123.525-100244392 A1
RHUF210WZRequest a Quote752.7116.1742.8164.725-100326509 A1
RHUF260WZRequest a Quote940.9145.2928.6205.925-100407599 A1
RHUF310WZRequest a Quote1129174.21117249.625-100488392/392 A2
RHUF365WZRequest a Quote1317196.31293281.425-100550509/392 A2
RHUF420WZRequest a Quote1505224.41478321.625-100628509/509 A2
RHUF470WZRequest a Quote1693252.51663361.925-100708599/509 A2
RHUF520WZRequest a Quote1881280.61847402.125-100786599/599 A2
  • Cooling: chilled water entering / leaving 12 / 7 °C; condenser water entering / leaving 25 / 30 °C. Heating: source water entering / leaving 10 / 5 °C; hot water entering / leaving 40 / 45 °C.
  • Evaporator and condenser fouling factors: 0.018 and 0.044 m²·°C/kW. Main power 380 V / 3 phase / 50 Hz; control 220 V / 1 phase / 50 Hz. R134a; twin-screw compressors.
  • Starting-current values are printed in A; slash-separated compressor values are not summed. Q selections have separate ratings and operating limits.
  • Manufacturer reference: Z0050069-260903; physical PDF page 6.

WZ — water-side and installation data

RHUF water / ground-source screw heat-pump selections; R134a.

WZ — water-side and installation data. RHUF water / ground-source screw heat-pump selections; R134a.
Model referenceChilled-water flow(m³/h)Chilled-water pressure drop(kPa)Heat-source-water flow(m³/h)Heat-source-water pressure drop(kPa)Evaporator flangeCondenser-water flow(m³/h)Condenser-water pressure drop(kPa)Hot-water flow(m³/h)Hot-water pressure drop(kPa)Condenser flangeNet weight(kg)Length(mm)Width(mm)Height(mm)
RHUF155WZRequest a Quote97.095374.631DN150112.17995.8458DN1503500332017002258
RHUF210WZRequest a Quote129.55399.4331DN150149.481127.859DN1503760332017002258
RHUF260WZRequest a Quote161.853124.331DN150186.883159.761DN1503930332017002258
RHUF310WZRequest a Quote194.263149.237DN200224.279192.158DN2006470469317662318
RHUF365WZRequest a Quote226.56517438DN200260.381222.459DN2006770469317662318
RHUF420WZRequest a Quote258.967198.939DN200297.583254.261DN2007070469317662318
RHUF470WZRequest a Quote291.269223.841DN200334.68528662DN2007320469317662318
RHUF520WZRequest a Quote323.571248.542DN200371.887317.764DN2007570469317662318
  • Cooling: chilled water entering / leaving 12 / 7 °C; condenser water entering / leaving 25 / 30 °C. Heating: source water entering / leaving 10 / 5 °C; hot water entering / leaving 40 / 45 °C.
  • Evaporator and condenser fouling factors: 0.018 and 0.044 m²·°C/kW. Main power 380 V / 3 phase / 50 Hz; control 220 V / 1 phase / 50 Hz. R134a; twin-screw compressors.
  • Starting-current values are printed in A; slash-separated compressor values are not summed. Q selections have separate ratings and operating limits.
  • Manufacturer reference: Z0050069-260903; physical PDF page 6.

WZ-Q — cooling and heating performance

RHUF water / ground-source screw heat-pump selections; R134a.

WZ-Q — cooling and heating performance. RHUF water / ground-source screw heat-pump selections; R134a.
Model referenceCooling capacity(kW)Cooling input(kW)Heating capacity(kW)Heating input(kW)Capacity control (%)Maximum current(A)Starting currentCompressors(count)
RHUF155WZ-QRequest a Quote564.588.82522.2128.925-100326599 A1
RHUF210WZ-QRequest a Quote752.7118.4696.2171.825-100435779 A1
RHUF310WZ-QRequest a Quote1129177.61047260.425-100652599/599 A2
RHUF365WZ-QRequest a Quote1317200.21211293.525-100735779/599 A2
RHUF420WZ-QRequest a Quote1505228.81384335.425-100840779/779 A2
  • Cooling: chilled water entering / leaving 12 / 7 °C; condenser water entering / leaving 25 / 30 °C. Heating: source water entering / leaving 10 / 5 °C; hot water entering / leaving 40 / 45 °C.
  • Evaporator and condenser fouling factors: 0.018 and 0.044 m²·°C/kW. Main power 380 V / 3 phase / 50 Hz; control 220 V / 1 phase / 50 Hz. R134a; twin-screw compressors.
  • Starting-current values are printed in A; slash-separated compressor values are not summed. Q selections have separate ratings and operating limits.
  • Manufacturer reference: Z0050069-260903; physical PDF page 6.

WZ-Q — water-side and installation data

RHUF water / ground-source screw heat-pump selections; R134a.

WZ-Q — water-side and installation data. RHUF water / ground-source screw heat-pump selections; R134a.
Model referenceChilled-water flow(m³/h)Chilled-water pressure drop(kPa)Heat-source-water flow(m³/h)Heat-source-water pressure drop(kPa)Evaporator flangeCondenser-water flow(m³/h)Condenser-water pressure drop(kPa)Hot-water flow(m³/h)Hot-water pressure drop(kPa)Condenser flangeNet weight(kg)Length(mm)Width(mm)Height(mm)
RHUF155WZ-QRequest a Quote97.095367.6526DN150112.47989.8251DN1503585332017002258
RHUF210WZ-QRequest a Quote129.55390.226DN150149.881119.752DN1503835332017002258
RHUF310WZ-QRequest a Quote194.263135.330DN200224.779180.151DN2006640469317662318
RHUF365WZ-QRequest a Quote226.565157.831DN20026181208.352DN2006930469317662318
RHUF420WZ-QRequest a Quote258.967180.432DN200298.28323853DN2007220469317662318
  • Cooling: chilled water entering / leaving 12 / 7 °C; condenser water entering / leaving 25 / 30 °C. Heating: source water entering / leaving 10 / 5 °C; hot water entering / leaving 40 / 45 °C.
  • Evaporator and condenser fouling factors: 0.018 and 0.044 m²·°C/kW. Main power 380 V / 3 phase / 50 Hz; control 220 V / 1 phase / 50 Hz. R134a; twin-screw compressors.
  • Starting-current values are printed in A; slash-separated compressor values are not summed. Q selections have separate ratings and operating limits.
  • Manufacturer reference: Z0050069-260903; physical PDF page 6.

Key configuration options

  • Standard WZP and WZ, and the separate WZP-Q / WZ-Q configurations, retain individual performance and hydraulic tables.
  • Source operating limits: RHUF50–130WZP chilled-water leaving 5–20 °C; the other listed groups 4–15 °C. Condenser-water leaving 22–40 °C.
  • Hot-water leaving limits: RHUF50–130WZP and the listed Q groups 35–60 °C; RHUF150–521WZP and RHUF155–520WZ standard groups 35–45 °C. A 60 °C limit does not assign a 60 °C capacity to every model.
  • Water quality, source-side heat exchanger arrangement, pressure rating and ground-loop design conditions require project review.

Applications

  • Commercial and industrial heating / cooling projects with a suitable water or ground-loop heat source.
  • Project equipment selection based on source-water availability, load profile and hydraulic requirements.

Information for equipment selection

  • Complete RHUF model, standard or Q configuration and required quantity.
  • Cooling / heating loads; source-water, chilled-water and hot-water entering / leaving temperatures and flows.
  • Water quality, pressure rating, power supply, plant-room access and destination country.

Application suitability requires a review of the project requirements and selected model.

Project equipment procurement

Delta M&E reviews equipment requirements, manufacturer selections and supply arrangements for each inquiry. Send your BOQ or equipment schedule to discuss the required model, documentation and destination.

Technical documents

No model-specific technical documents are available for download on this page. Request Technical Information

Related series

REQUEST A QUOTE / TECHNICAL INFORMATION

Prepare your equipment requirements

Product reference: Hitachi WZP / WZ Water-Source Screw Heat Pumps

Prepare your BOQ or model list, quantity, project location, design conditions and power supply. For stock inquiries, confirm the exact model, condition, export suitability and delivery requirements.

Request a Quote

Email your requirements to [email protected]. You can include your BOQ or equipment schedule. See what to include in your inquiry.