Hitachi Cooling & Heating / SERIES OVERVIEW

Hitachi SMART+ Inverter Modular Chillers & Heat Pumps

R410A inverter scroll modular equipment; RCUA / RHUA AVE

Brand
Hitachi Cooling & Heating
Series
SMART+ / AVE
Equipment category
Heat Pumps

Product overview

SMART+ uses AVE modules with 65, 130 and 150 kW standard cooling selections. RCUA references identify cooling-only equipment; RHUA references include separately rated heating. The AVE table lists its own compressor counts, water connections, current and model-specific weight. It is an alternative selection to SMART AVS, rather than an extension of the AVSH multifunction performance table.

Key technical specifications

Match the complete model and configuration to your design duty. Compare ratings only at the stated water and ambient conditions; then send the model reference, quantity and project requirements for review.

Scroll each table horizontally to compare all columns. Model references remain visible as you scroll.

SMART+ / AVE — cooling-only models

Literal RCUA model codes; no heating duty is assigned.

SMART+ / AVE — cooling-only models. Literal RCUA model codes; no heating duty is assigned.
Model referenceCooling capacity(kW)Cooling input(kW)Cooling rated current(A)
RCUA065AVERequest a Quote6521.537
RCUA130AVERequest a Quote1304374
RCUA150AVERequest a Quote15049.282
  • Cooling: leaving chilled water 7 °C, water-flow coefficient 0.172 m³/(h·kW), outdoor air 35 °C dry bulb.
  • Heating: leaving water 45 °C, water-flow coefficient 0.172 m³/(h·kW), outdoor dry bulb / wet bulb 7 / 6 °C.
  • Water-side fouling factor 0.018 m²·°C/kW. Main supply 380 V / 3 phase / 50 Hz; R410A. Ratings do not establish 60 Hz suitability.
  • Control DC 24 V. RCUA is cooling-only; RHUA has separate heating ratings. Noise conditions are not a project-site guarantee.
  • Manufacturer reference: Z0050037-251008; physical PDF page 9.

SMART+ / AVE — heat-pump models

Literal RHUA model codes with independent heating data.

SMART+ / AVE — heat-pump models. Literal RHUA model codes with independent heating data.
Model referenceCooling capacity(kW)Cooling input(kW)Heating capacity(kW)Heating input(kW)CSPF(kW/kW)Cooling rated current(A)Heating rated current(A)
RHUA065AVERequest a Quote6521.56621.84.433738
RHUA130AVERequest a Quote1304313243.74.437476
RHUA150AVERequest a Quote15049.2160504.458283
  • Cooling: leaving chilled water 7 °C, water-flow coefficient 0.172 m³/(h·kW), outdoor air 35 °C dry bulb.
  • Heating: leaving water 45 °C, water-flow coefficient 0.172 m³/(h·kW), outdoor dry bulb / wet bulb 7 / 6 °C.
  • Water-side fouling factor 0.018 m²·°C/kW. Main supply 380 V / 3 phase / 50 Hz; R410A. Ratings do not establish 60 Hz suitability.
  • Control DC 24 V. RCUA is cooling-only; RHUA has separate heating ratings. Noise conditions are not a project-site guarantee.
  • Manufacturer reference: Z0050037-251008; physical PDF page 9.

SMART+ / AVE — installation and electrical data

Cooling-only and heat-pump weights follow the complete model code.

SMART+ / AVE — installation and electrical data. Cooling-only and heat-pump weights follow the complete model code.
Model referenceMain power supplyRefrigerantRefrigerant circuits(count)Compressors(count)Compressor typeCapacity control (%)Water heat exchangerWater flow(m³/h)Water pressure drop(kPa)Water connectionFans(count)Fan input (as printed)(kW)Total airflow(m³/h)Length(mm)Width(mm)Height(mm)Net weight(kg)Maximum current(A)
RCUA065AVERequest a Quote380 V / 3 phase / 50 HzR410A11Inverter scroll100–25.0Plate11.1855DN50 grooved11.52150012111060239042050
RHUA065AVERequest a Quote380 V / 3 phase / 50 HzR410A11Inverter scroll100–25.0Plate11.1855DN50 grooved11.52150012111060239046050
RCUA130AVERequest a Quote380 V / 3 phase / 50 HzR410A22Inverter scroll100–25.0Plate22.3640DN65 grooved2343000223710602390775100
RHUA130AVERequest a Quote380 V / 3 phase / 50 HzR410A22Inverter scroll100–25.0Plate22.3640DN65 grooved2343000223710602390845100
RCUA150AVERequest a Quote380 V / 3 phase / 50 HzR410A22Inverter scroll100–25.0Plate25.840DN65 grooved23.647400247811002390880128
RHUA150AVERequest a Quote380 V / 3 phase / 50 HzR410A22Inverter scroll100–25.0Plate25.840DN65 grooved23.647400247811002390960128
  • Cooling: leaving chilled water 7 °C, water-flow coefficient 0.172 m³/(h·kW), outdoor air 35 °C dry bulb.
  • Heating: leaving water 45 °C, water-flow coefficient 0.172 m³/(h·kW), outdoor dry bulb / wet bulb 7 / 6 °C.
  • Water-side fouling factor 0.018 m²·°C/kW. Main supply 380 V / 3 phase / 50 Hz; R410A. Ratings do not establish 60 Hz suitability.
  • Control DC 24 V. RCUA is cooling-only; RHUA has separate heating ratings. Noise conditions are not a project-site guarantee.
  • Manufacturer reference: Z0050037-251008; physical PDF page 9.

Key configuration options

  • Six complete AVE codes are listed: three RCUA cooling-only models and three RHUA heat-pump models. No heating capacity is assigned to RCUA.
  • The RHUA150AVE standard heating selection is 160 kW at the stated test point; this is distinct from its 150 kW cooling rating.
  • Use AVE-specific module dimensions, compressor count and weights. SMART AVS / AVSH imagery and technical values are not substituted here.

Applications

  • Commercial cooling-only or reversible water-system equipment procurement.
  • Projects comparing AVE module size, water connections and electrical load before a manufacturer selection.

Information for equipment selection

  • Complete RCUA or RHUA AVE model and quantity; cooling-only or heating / cooling requirements.
  • Design loads, entering / leaving water temperatures, flow, ambient conditions and power supply.
  • Module arrangement, available installation space, control scope and destination country.

Application suitability requires a review of the project requirements and selected model.

Project equipment procurement

Delta M&E reviews equipment requirements, manufacturer selections and supply arrangements for each inquiry. Send your BOQ or equipment schedule to discuss the required model, documentation and destination.

Technical documents

No model-specific technical documents are available for download on this page. Request Technical Information

Related series

REQUEST A QUOTE / TECHNICAL INFORMATION

Prepare your equipment requirements

Product reference: Hitachi SMART+ Inverter Modular Chillers & Heat Pumps

Prepare your BOQ or model list, quantity, project location, design conditions and power supply. For stock inquiries, confirm the exact model, condition, export suitability and delivery requirements.

Request a Quote

Email your requirements to [email protected]. You can include your BOQ or equipment schedule. See what to include in your inquiry.