Hitachi Cooling & Heating / SERIES OVERVIEW

Hitachi SMART Inverter Modular Chillers & Heat Pumps

Air-cooled inverter scroll equipment; ordinary AVS / multifunction AVSH

Brand
Hitachi Cooling & Heating
Series
SMART / AVS / AVSH
Equipment category
Heat Pumps
Hitachi SMART / AVS inverter modular chiller and heat pump series

Product overview

SMART offers ordinary AVS chilled-water and heat-pump selections alongside multifunction AVSH equipment. AVSH has separately rated cooling, space-heating, domestic-hot-water and cooling-with-heat-recovery modes. Its hydraulic circuits and installation data differ from ordinary AVS. Compare the required operating mode rather than adding capacities from different test conditions.

Key technical specifications

Match the complete model and configuration to your design duty. Compare ratings only at the stated water and ambient conditions; then send the model reference, quantity and project requirements for review.

Scroll each table horizontally to compare all columns. Model references remain visible as you scroll.

SMART / AVS — ordinary cooling

Ordinary AVS selection; separate from multifunction AVSH.

SMART / AVS — ordinary cooling. Ordinary AVS selection; separate from multifunction AVSH.
Model referenceCooling capacity(kW)Cooling input(kW)Cooling rated current(A)
RH(C)UA065AVSRequest a Quote6520.938
RH(C)UA130AVSRequest a Quote1304276
  • Cooling: leaving chilled water 7 °C, water-flow coefficient 0.172 m³/(h·kW), outdoor air 35 °C dry bulb.
  • Heating ratings apply only to the heat-pump configuration. Leaving hot water 45 °C, water-flow coefficient 0.172 m³/(h·kW); the source states outdoor wet bulb 6 °C without a dry-bulb value in this table note.
  • Water-side fouling factor 0.018 m²·°C/kW. Main supply 380 V / 3 phase / 50 Hz; R410A. Ratings do not establish 60 Hz suitability.
  • Ordinary AVS printed model patterns are selection references, not fully expanded order codes. Cooling-only and heat-pump weights are separate; heating ratings apply only to the heat-pump selection.
  • Control supply DC 24 V. Full-load / low-noise-mode sound values are distinct measurements in dB, not an N-suffix product configuration.
  • Manufacturer reference: Z0050036-251008; physical PDF page 9.

SMART / AVS — ordinary heat-pump ratings

Heat-pump branch only; not applicable to cooling-only selection.

SMART / AVS — ordinary heat-pump ratings. Heat-pump branch only; not applicable to cooling-only selection.
Model referenceHeating capacity(kW)Heating input(kW)CSPF(—)Heating rated current(A)
RH(C)UA065AVSRequest a Quote6621.84.2940
RH(C)UA130AVSRequest a Quote13243.74.2978
  • Cooling: leaving chilled water 7 °C, water-flow coefficient 0.172 m³/(h·kW), outdoor air 35 °C dry bulb.
  • Heating ratings apply only to the heat-pump configuration. Leaving hot water 45 °C, water-flow coefficient 0.172 m³/(h·kW); the source states outdoor wet bulb 6 °C without a dry-bulb value in this table note.
  • Water-side fouling factor 0.018 m²·°C/kW. Main supply 380 V / 3 phase / 50 Hz; R410A. Ratings do not establish 60 Hz suitability.
  • Ordinary AVS printed model patterns are selection references, not fully expanded order codes. Cooling-only and heat-pump weights are separate; heating ratings apply only to the heat-pump selection.
  • Control supply DC 24 V. Full-load / low-noise-mode sound values are distinct measurements in dB, not an N-suffix product configuration.
  • Manufacturer reference: Z0050036-251008; physical PDF page 9.

SMART / AVS — ordinary module data

Cooling-only and heat-pump configurations retain separate weights.

SMART / AVS — ordinary module data. Cooling-only and heat-pump configurations retain separate weights.
Model referenceMain power supplyRefrigerantRefrigerant circuits(count)Compressors(count)Compressor typeCapacity control (%)Water heat exchangerWater flow(m³/h)Water pressure drop(kPa)Water connectionFans(count)Fan input (as printed)(kW)Total airflow(m³/h)Length(mm)Width(mm)Height(mm)Cooling-only net weight(kg)Heat-pump net weight(kg)Maximum current(A)Full-load noise(dB)Low-noise-mode noise(dB)
RH(C)UA065AVSRequest a Quote380 V / 3 phase / 50 HzR410A12Inverter scroll100–25.0Plate11.1855DN50 grooved11.6521500137012002410485520486863
RH(C)UA130AVSRequest a Quote380 V / 3 phase / 50 HzR410A24Inverter scroll100–25.0Plate22.3640DN65 grooved23.343000243812002410875945967166
  • Cooling: leaving chilled water 7 °C, water-flow coefficient 0.172 m³/(h·kW), outdoor air 35 °C dry bulb.
  • Heating ratings apply only to the heat-pump configuration. Leaving hot water 45 °C, water-flow coefficient 0.172 m³/(h·kW); the source states outdoor wet bulb 6 °C without a dry-bulb value in this table note.
  • Water-side fouling factor 0.018 m²·°C/kW. Main supply 380 V / 3 phase / 50 Hz; R410A. Ratings do not establish 60 Hz suitability.
  • Ordinary AVS printed model patterns are selection references, not fully expanded order codes. Cooling-only and heat-pump weights are separate; heating ratings apply only to the heat-pump selection.
  • Control supply DC 24 V. Full-load / low-noise-mode sound values are distinct measurements in dB, not an N-suffix product configuration.
  • Manufacturer reference: Z0050036-251008; physical PDF page 9.

SMART / AVSH — multifunction cooling (A)

Multifunction configuration; independent from ordinary AVS.

SMART / AVSH — multifunction cooling (A). Multifunction configuration; independent from ordinary AVS.
Model referenceCooling capacity(kW)Cooling input(kW)Cooling ratio (source label: COP)(—)CSPF(—)
RHUA065AVSHRequest a Quote63.520.43.114.29
RHUA130AVSHRequest a Quote130423.14.29
  • A — cooling: leaving chilled water 7 °C, water-flow coefficient 0.172 m³/(h·kW), outdoor air 35 °C dry bulb.
  • B — heating and C — domestic hot water: leaving water 45 °C, water-flow coefficient 0.172 m³/(h·kW), outdoor air dry bulb / wet bulb 7 / 6 °C.
  • D — cooling with heat recovery: chilled-water leaving 7 °C and outdoor air 35 °C dry bulb; recovered hot-water leaving 45 °C. The printed water-flow coefficient is 0.172 m³/(h·kW) for both circuits.
  • The source labels its cooling ratio COP and heating / domestic-water ratios EER; labels and values are retained, not silently relabelled. Each mode has its own duties; these capacities must not be added as simultaneous output.
  • Main supply 380 V / 50 Hz; control DC 24 V; R410A. Water-side design pressure 1.0 MPa. Water-flow switch is customer supplied. Noise is a semi-anechoic test, not a site guarantee.
  • Manufacturer reference: Z0050036-251008; physical PDF page 9.

SMART / AVSH — heating (B)

Space-heating mode of the multifunction configuration.

SMART / AVSH — heating (B). Space-heating mode of the multifunction configuration.
Model referenceHeating capacity(kW)Heating input(kW)Heating ratio (source label: EER)(—)
RHUA065AVSHRequest a Quote6621.83.03
RHUA130AVSHRequest a Quote13243.73.02
  • A — cooling: leaving chilled water 7 °C, water-flow coefficient 0.172 m³/(h·kW), outdoor air 35 °C dry bulb.
  • B — heating and C — domestic hot water: leaving water 45 °C, water-flow coefficient 0.172 m³/(h·kW), outdoor air dry bulb / wet bulb 7 / 6 °C.
  • D — cooling with heat recovery: chilled-water leaving 7 °C and outdoor air 35 °C dry bulb; recovered hot-water leaving 45 °C. The printed water-flow coefficient is 0.172 m³/(h·kW) for both circuits.
  • The source labels its cooling ratio COP and heating / domestic-water ratios EER; labels and values are retained, not silently relabelled. Each mode has its own duties; these capacities must not be added as simultaneous output.
  • Main supply 380 V / 50 Hz; control DC 24 V; R410A. Water-side design pressure 1.0 MPa. Water-flow switch is customer supplied. Noise is a semi-anechoic test, not a site guarantee.
  • Manufacturer reference: Z0050036-251008; physical PDF page 9.

SMART / AVSH — domestic hot water (C)

Dedicated domestic-water duty; separate from heat recovery.

SMART / AVSH — domestic hot water (C). Dedicated domestic-water duty; separate from heat recovery.
Model referenceDomestic-water heating capacity(kW)Domestic-water heating input(kW)Domestic-water ratio (source label: EER)(—)
RHUA065AVSHRequest a Quote6320.83.03
RHUA130AVSHRequest a Quote12641.73.02
  • A — cooling: leaving chilled water 7 °C, water-flow coefficient 0.172 m³/(h·kW), outdoor air 35 °C dry bulb.
  • B — heating and C — domestic hot water: leaving water 45 °C, water-flow coefficient 0.172 m³/(h·kW), outdoor air dry bulb / wet bulb 7 / 6 °C.
  • D — cooling with heat recovery: chilled-water leaving 7 °C and outdoor air 35 °C dry bulb; recovered hot-water leaving 45 °C. The printed water-flow coefficient is 0.172 m³/(h·kW) for both circuits.
  • The source labels its cooling ratio COP and heating / domestic-water ratios EER; labels and values are retained, not silently relabelled. Each mode has its own duties; these capacities must not be added as simultaneous output.
  • Main supply 380 V / 50 Hz; control DC 24 V; R410A. Water-side design pressure 1.0 MPa. Water-flow switch is customer supplied. Noise is a semi-anechoic test, not a site guarantee.
  • Manufacturer reference: Z0050036-251008; physical PDF page 9.

SMART / AVSH — cooling with heat recovery (D)

Paired ratings at the source heat-recovery test condition.

SMART / AVSH — cooling with heat recovery (D). Paired ratings at the source heat-recovery test condition.
Model referenceRecovered heat(kW)Cooling in heat-recovery mode(kW)Heat-recovery-mode input(kW)
RHUA065AVSHRequest a Quote805821.4
RHUA130AVSHRequest a Quote16011743.3
  • A — cooling: leaving chilled water 7 °C, water-flow coefficient 0.172 m³/(h·kW), outdoor air 35 °C dry bulb.
  • B — heating and C — domestic hot water: leaving water 45 °C, water-flow coefficient 0.172 m³/(h·kW), outdoor air dry bulb / wet bulb 7 / 6 °C.
  • D — cooling with heat recovery: chilled-water leaving 7 °C and outdoor air 35 °C dry bulb; recovered hot-water leaving 45 °C. The printed water-flow coefficient is 0.172 m³/(h·kW) for both circuits.
  • The source labels its cooling ratio COP and heating / domestic-water ratios EER; labels and values are retained, not silently relabelled. Each mode has its own duties; these capacities must not be added as simultaneous output.
  • Main supply 380 V / 50 Hz; control DC 24 V; R410A. Water-side design pressure 1.0 MPa. Water-flow switch is customer supplied. Noise is a semi-anechoic test, not a site guarantee.
  • Manufacturer reference: Z0050036-251008; physical PDF page 9.

SMART / AVSH — water circuits and module data

Heating / cooling and domestic-water circuits remain separate.

SMART / AVSH — water circuits and module data. Heating / cooling and domestic-water circuits remain separate.
Model referenceRefrigerant circuits(count)Compressors(count)Compressor typeCapacity control (%)Water heat exchangerCooling / heating water flow(m³/h)Cooling / heating pressure drop(kPa)Cooling / heating connectionHeat-recovery water flow(m³/h)Heat-recovery pressure drop(kPa)Domestic-water flow(m³/h)Domestic-water pressure drop(kPa)Domestic-water connectionFans(count)Fan input (as printed)(kW)Total airflow(m³/h)Length(mm)Width(mm)Height(mm)Net weight(kg)Standard noise(dB)Quiet-mode noise(dB)
RHUA065AVSHRequest a Quote12Inverter scroll100–25.0Stainless-steel plate10.9255DN50 grooved13.767510.8450DN50 grooved11.65215001572120024106306863
RHUA130AVSHRequest a Quote24Inverter scroll100–25.0Stainless-steel plate22.3640DN65 grooved27.525021.6730DN65 flange23.34300027781200241011607166
  • A — cooling: leaving chilled water 7 °C, water-flow coefficient 0.172 m³/(h·kW), outdoor air 35 °C dry bulb.
  • B — heating and C — domestic hot water: leaving water 45 °C, water-flow coefficient 0.172 m³/(h·kW), outdoor air dry bulb / wet bulb 7 / 6 °C.
  • D — cooling with heat recovery: chilled-water leaving 7 °C and outdoor air 35 °C dry bulb; recovered hot-water leaving 45 °C. The printed water-flow coefficient is 0.172 m³/(h·kW) for both circuits.
  • The source labels its cooling ratio COP and heating / domestic-water ratios EER; labels and values are retained, not silently relabelled. Each mode has its own duties; these capacities must not be added as simultaneous output.
  • Main supply 380 V / 50 Hz; control DC 24 V; R410A. Water-side design pressure 1.0 MPa. Water-flow switch is customer supplied. Noise is a semi-anechoic test, not a site guarantee.
  • Manufacturer reference: Z0050036-251008; physical PDF page 9.

Key configuration options

  • Ordinary RH(C)UA065AVS and RH(C)UA130AVS remain printed selection patterns. The complete cooling-only or heat-pump order code requires confirmation.
  • RHUA065AVSH and RHUA130AVSH are the multifunction references. Their A / B / C / D test points and water-circuit duties are listed separately from ordinary AVS.
  • SMART uses the AVS / AVSH references. SMART+ uses AVE references and its own module, compressor, electrical and weight data; the tables are not interchangeable.
  • The low-noise operating-mode values in the SMART table are not an N-suffix model family. Confirm the control mode and acoustic requirements for the project.

Applications

  • Commercial projects selecting ordinary chilled-water / heat-pump modules.
  • Projects evaluating a manufacturer-selected multifunction unit with distinct domestic-water and heat-recovery duties.

Information for equipment selection

  • Ordinary AVS or multifunction AVSH selection, complete reference, quantity and required operating modes.
  • Separate cooling, heating and domestic-water duties, water temperatures and heat-recovery requirements.
  • Water-circuit arrangement, available power, space, acoustic constraints and destination country.

Application suitability requires a review of the project requirements and selected model.

Project equipment procurement

Delta M&E reviews equipment requirements, manufacturer selections and supply arrangements for each inquiry. Send your BOQ or equipment schedule to discuss the required model, documentation and destination.

Technical documents

No model-specific technical documents are available for download on this page. Request Technical Information

Related series

REQUEST A QUOTE / TECHNICAL INFORMATION